2006-02-07 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED
  
 2.)SHOW MANEUVERING CLEARANCE FOR THE
 FOLLOWING DOORS, FBC11-4.13.6, FIGURE
 25: EXAM ROOM 1, PUSH SIDE; WAITING ROOM
 PULL SIDE; OFFICE 104 PUSH SIDE
  
 3.)ARE ANY TENANT SEPARATIONS
 AFFECTED?
  
 4.)A1, DEMOLITION NOTES, ITEM 3 REFERS
 TO A RESIDENCE.ADDRESS.
  
 5.)NO EXITING INFORMATION WAS
 PROVIDED.HOW DOES THE CHANGE IN THE
 PLAN AFFECT MEANS OF EGRESS?SHOW
 COMPLIANCE WITH FBC10 ON THE PLAN.
  
 6.)DECLARE GOVERNING CODE.
  
 7.)INDEX REFERS TO A SHEET A3 WHICH IS
 NOT A PART OF THE PLAN SUBMITTED.
 ADDRESS.