Plan Review Notes For Permit 05110837 |
Permit Number |
05110837 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-01-05 00:00:00 | DENIED | | | | REFERENCE: FBC-2004 FUEL GAS | | | | ON AN 0.5 PSI OR LESS INLET PRESSURE | | NATURAL GAS SYSTEM, ALL SYSTEM PIPES | | SHALL HAVE THE SAME INLET PRESSURE OF | | 0.5 PSI OR LESS AND PRESSURE DROP OF | | 0.5 IN OF WC PER TABLES | | 404.4(2) SCH. 40 METALLIC PIPE | | 402.4(14) CSST | | 402.4(20) PE | | NOTE:PER FLORIDA PUBLIC UTILITIES THE | | MAXIMUM DELIVERY PRESSURE AFTER THE | | METER IS 11 INCH WATER COL. | | DENIED | | | | REFERENCE: FBC-2004 FUEL GAS | | | | ON AN 0.5 PSI OR LESS INLET PRESSURE | | NATURAL GAS SYSTEM, ALL SYSTEM PIPES | | SHALL HAVE THE SAME INLET PRESSURE OF | | 0.5 PSI OR LESS AND PRESSURE DROP OF 0.5 | | IN OF WC PER TABLES | | 402.4(2) SCH. 40 METALLIC PIPE | | 402.4(14) CSST | | 402.4(20) PE | | NOTE: PER FLORIDA PUBLIC UTILITIES THE | | MAXIMUM DELIVERY PRESSURE AFTER THE | | METER IS 11 INCH WATER COL. | | | | ANY QUESTIONS REGUARDING THESE | | REQUIREMENTS MAY BE REFERRED TO: | | | | PLAN REVIEW BY MIKE PERSON | | (561)805-6730 | | FAX (561)805-6731 | | E-MAIL [email protected] | | OR | | CHEIF PLUMBING INSPECTOR | | PAUL SCHMITZ (561)805-6692 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|