2006-08-23 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 05110836 |
| ADD: 1122 PALM BEACH LAKES |
| CONT: POMEROY ELECTRIC, INC. |
| TEL: (954)427-0705 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) THE WIND LOAD CALCULATIONS INDICATE |
| THE DESIGN CRITERIA AS ASCE 7-04. THE |
| 2004 FBC BUILDING USES ASCE 7-02 SEE |
| CHAPTER 35 FOR REFRENCED STANDARDS. |
| |
| 2) SHEET 2OF 7 S1 USES 8/3 WHICH SHOULD |
| BE 9/3. |
| |
| 3) SHEET 3OF 7 PAGES 37' POLE, (POLE |
| TYPE I) INDICATE SOME TYPE OF TAMPERING |
| WITH THE PRINTED NUMBERS. THE PRINTED OR |
| TAMPERED NUMBERS REPRESENT A 37' POLE |
| INSAND WHERE AS THE DIAGRAM AT LEFT |
| INDICATES A 34'-0" OVERALL LENGTH. |
| EMBEDMENT IN SAND.106.1.2* |
| |
| 4) WHAT DOES EPA STAND FOR? WHY IS THE |
| 120 & 150 MPH WIND ZONES ELIMINATED |
| WHEREAS THE TYPE II POLE HASA ALL 3 |
| CATAGORIES FILED IN? AGAIN TAMPERED |
| WITH.106.1.2* |
| |
| 5) SHEET POLE TYPE II, 37' EMBEDMENT IN |
| ROCKWHY IS THERE A DIFERENCE IN WEIGHT |
| |
| IF BOTH POLE TYPE 1 & POLE TYPE II BOTH |
| ARE 37' LONG, A 280 LB DIFFERENCE? |
| 106.1.2* |
| |
| 6) THE ES-1 SHEEET DOES NOT INDICATE IF |
| THE POLES TO BE USED ARE A 37' TYPE I |
| POLE OR A 37' TYPE II POLE? ADDITIONAL |
| INFORMATION? 106.1.2* |