2006-08-23 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05110836
 ADD: 1122 PALM BEACH LAKES
 CONT: POMEROY ELECTRIC, INC.
 TEL: (954)427-0705
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE WIND LOAD CALCULATIONS INDICATE
 THE DESIGN CRITERIA AS ASCE 7-04. THE
 2004 FBC BUILDING USES ASCE 7-02 SEE
 CHAPTER 35 FOR REFRENCED STANDARDS.
  
 2) SHEET 2OF 7 S1 USES 8/3 WHICH SHOULD
 BE 9/3.
  
 3) SHEET 3OF 7 PAGES 37' POLE, (POLE
 TYPE I) INDICATE SOME TYPE OF TAMPERING
 WITH THE PRINTED NUMBERS. THE PRINTED OR
 TAMPERED NUMBERS REPRESENT A 37' POLE
 INSAND WHERE AS THE DIAGRAM AT LEFT
 INDICATES A 34'-0" OVERALL LENGTH.
 EMBEDMENT IN SAND.106.1.2*
  
 4) WHAT DOES EPA STAND FOR? WHY IS THE
 120 & 150 MPH WIND ZONES ELIMINATED
 WHEREAS THE TYPE II POLE HASA ALL 3
 CATAGORIES FILED IN? AGAIN TAMPERED
 WITH.106.1.2*
  
 5) SHEET POLE TYPE II, 37' EMBEDMENT IN
 ROCKWHY IS THERE A DIFERENCE IN WEIGHT
  
 IF BOTH POLE TYPE 1 & POLE TYPE II BOTH
 ARE 37' LONG, A 280 LB DIFFERENCE?
 106.1.2*
  
 6) THE ES-1 SHEEET DOES NOT INDICATE IF
 THE POLES TO BE USED ARE A 37' TYPE I
 POLE OR A 37' TYPE II POLE? ADDITIONAL
 INFORMATION? 106.1.2*
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  