Plan Review Notes For Permit 05110768 |
Permit Number |
05110768 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-06-08 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} 210.52(A) GENERAL PROVISIONS. IN | | EVERY KITCHEN, FAMILY ROOM, DINING ROOM, | | LIVING ROOM, PARLOR, LIBRARY, DEN, | | SUNROOM, BEDROOM, RECREATION ROOM, OR | | SIMILAR ROOM OR AREA OF DWELLING UNITS, | | RECEPTACLE OUTLETS SHALL BE INSTALLED IN | | ACCORDANCE WITH THE GENERAL PROVISIONS | | SPECIFIED IN 210.52(A)(1) THROUGH | | (A)(3). | | (1) SPACING. RECEPTACLES SHALL BE | | INSTALLED SO THAT NO POINT MEASURED | | HORIZONTALLY ALONG THE FLOOR LINE IN ANY | | WALL SPACE IS MORE THAN 1.8 M (6 FT) | | FROM A RECEPTACLE OUTLET. | | | | PLEASE HAVE THE PERSON RESPONSIBLE FOR | | DRAWING THE PLAN PRINT AND SIGN THEIR | | NAME TO SAME. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|