Plan Review Notes
Plan Review Notes For Permit 05110655
Permit Number 05110655
Review Stop P
Sequence Number 2
Notes
Date Text
2006-01-17 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 1. SHTS L100 THRU L700 AND IR100 & IR500
 THE CERTIFICATE OF AUTHORIZATION NUMBER
 FOR THE LANDSCAPE ARCHITECT BUSINESS IS
 REQUIRED IN THE TITLE BLOCK OF EACH
 SHEET. FAC T1G1-16.004(2) & FS 481.319.
 3. SHT A-401 ACCESSIBLE TOILET ROOM
 DETAIL. THE FOLLOWING INFORMATION IS
 REQUIRED TO SHOW COMPLIANCE WITH CHAPTER
 11:
 FOR LAVS:
 A. 11-4.19.2 CLEARANCES
 C. 11-4.19.5 FAUCETS
 6. SHT P-401 FLOOR SINK OR HUB DRAIN IS
 REQUIRED FOR THE ICE MACHINE. SECTION
 802.1 - (FLOOR DRAINS ARE NOT APPROVED
 INDIRECT WASTE RECEPTORS).
 10. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMITS. (NATURAL
 FOR THE STRUCTURE, AND LP FOR THE
 GENERATOR):
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - NOT ALL LENGTHS FOR
 EACH SECTION SHOWN. - STILL MISSING SOME
 LENGTHS FOR CUT SECTIONS. (NEW COMMENT -
 RISER DIAGRAM DOES NOT REFLECT THE FLOOR
 PLAN IN SOME AREAS).
 C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). - TOTAL CONNECTED CAPACITY IS
 INDICATED AS 698,000 CFH. PLEASE
 CLARIFY. SECTION 106.1.1. - THIS STILL
 ADDS UP TO A DIFFERENT NUMBER (634,000
 BTU'S).
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - ADDING UP
 MEASUREMENTS SUBMITTED ON GAS RISER
 DIAGRAM, THE TOTAL DEVELOPED LENGTH IS
 CLOSE TO 200FT. PLEASE RECHECK LENGTH TO
 THE MOST REMOTE OUTLET. - THIS HAS NOT
 BEEN ADDRESSED.
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304. - INDICATE CUBIC
 FEET OF THE ROOM THE GAS DRYER IS IN TO
 DETERMINE IF IT IS IN A CONFINED SPACE.
 - NOT ADDRESSED.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 ****************NEW COMMENTS************
 1B. PIPE SIZING FOR GAS ISOMETRIC DOES
 NOT REFLECT THE TABLE FOR SEMIRIGID
 COPPER TUBING (402.4(8)). PLEASE RECHECK
 PIPE SIZES.
 2B. PROVIDE AN APPROVED TABLE FOR 5.0
 PSI FOR POLYETHYLENE TUBING FOR SYSTEM
 TO THE GENERATOR. TOTAL DISTANCE OF 200'
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]