2006-01-17 00:00:00 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 FUEL GAS |
| FBC-2001 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| FROM PREVIOUS REVIEW: |
| 1. SHTS L100 THRU L700 AND IR100 & IR500 |
| THE CERTIFICATE OF AUTHORIZATION NUMBER |
| FOR THE LANDSCAPE ARCHITECT BUSINESS IS |
| REQUIRED IN THE TITLE BLOCK OF EACH |
| SHEET. FAC T1G1-16.004(2) & FS 481.319. |
| 3. SHT A-401 ACCESSIBLE TOILET ROOM |
| DETAIL. THE FOLLOWING INFORMATION IS |
| REQUIRED TO SHOW COMPLIANCE WITH CHAPTER |
| 11: |
| FOR LAVS: |
| A. 11-4.19.2 CLEARANCES |
| C. 11-4.19.5 FAUCETS |
| 6. SHT P-401 FLOOR SINK OR HUB DRAIN IS |
| REQUIRED FOR THE ICE MACHINE. SECTION |
| 802.1 - (FLOOR DRAINS ARE NOT APPROVED |
| INDIRECT WASTE RECEPTORS). |
| 10. THE FOLLOWING INFORMATION IS |
| REQUIRED FOR THE GAS PERMITS. (NATURAL |
| FOR THE STRUCTURE, AND LP FOR THE |
| GENERATOR): |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. - NOT ALL LENGTHS FOR |
| EACH SECTION SHOWN. - STILL MISSING SOME |
| LENGTHS FOR CUT SECTIONS. (NEW COMMENT - |
| RISER DIAGRAM DOES NOT REFLECT THE FLOOR |
| PLAN IN SOME AREAS). |
| C. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). - TOTAL CONNECTED CAPACITY IS |
| INDICATED AS 698,000 CFH. PLEASE |
| CLARIFY. SECTION 106.1.1. - THIS STILL |
| ADDS UP TO A DIFFERENT NUMBER (634,000 |
| BTU'S). |
| D. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). - ADDING UP |
| MEASUREMENTS SUBMITTED ON GAS RISER |
| DIAGRAM, THE TOTAL DEVELOPED LENGTH IS |
| CLOSE TO 200FT. PLEASE RECHECK LENGTH TO |
| THE MOST REMOTE OUTLET. - THIS HAS NOT |
| BEEN ADDRESSED. |
| E. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| GAS CODE SECTION 304. - INDICATE CUBIC |
| FEET OF THE ROOM THE GAS DRYER IS IN TO |
| DETERMINE IF IT IS IN A CONFINED SPACE. |
| - NOT ADDRESSED. |
| G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| |
| ****************NEW COMMENTS************ |
| 1B. PIPE SIZING FOR GAS ISOMETRIC DOES |
| NOT REFLECT THE TABLE FOR SEMIRIGID |
| COPPER TUBING (402.4(8)). PLEASE RECHECK |
| PIPE SIZES. |
| 2B. PROVIDE AN APPROVED TABLE FOR 5.0 |
| PSI FOR POLYETHYLENE TUBING FOR SYSTEM |
| TO THE GENERATOR. TOTAL DISTANCE OF 200' |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |