2005-12-07 00:00:00 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 FUEL CODE |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. SHTS L100 THRU L700 AND IR100, IR500. |
| THE CERTIFICATE OF AUTHORIZATION NUMBER |
| FOR THE LANDSCAPE ARCHITECT BUSINESS IS |
| REQUIRED IN THE TITLE BLOCK OF EACH |
| SHEET. FAC 61G1-16.004(2). THE PRINTED |
| NAME OF THE PERSON SEALING THE DOCUMENT |
| IS REQUIRED ON EACH SHEET. FAC |
| 61G1-16.004(6). FS 481.319 & 481.2055 |
| 2. A-105 EQUIPMENT ACCESSORIES SCHEDULE |
| NUMBERS 43, 44, & 45. MORE INFORMATION |
| IS REQUIRED. SUBMIT MANUF. SPECIFICATION |
| SHEETS FOR THE COMPRESSOR, STORAGE, AND |
| FILL STATION FOR THIS SYSTEM. SECTION |
| 106.1.2. |
| 3. SHT A-401 ACCESSIBLE TOILET ROOM |
| DETAIL. THE FOLLOWING INFORMATION IS |
| REQUIRED TO SHOW COMPLIANCE WITH CHAPTER |
| 11: |
| FOR W/C'S: |
| A. 11-4.16.3 HEIGHT |
| B. 11-4.16.5 FLUSH CONTROLS |
| C. W/C'S TO BE 18" OFF WALL TO CENTER |
| OF FIXTURE. (FIG. 28) |
| FOR LAVS: |
| A. 11-4.19.2 CLEARANCES |
| B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| C. 11-4.19.5 FAUCETS |
| FOR SHOWERS: |
| A. 11-4.21.2 SIZE AND CLEARNACES |
| B. 11-4.21.3 SEAT |
| C. 11-4.21.5 CONTROLS |
| D. 11-4.21.6 SHOWER UNIT |
| E. 11-4.21.7 CURBS |
| 4. PER TABLE 403.1 A DRINKING FOUNTAIN |
| IS REQUIRED. SUBMIT A DETAIL SHOWING |
| COMPLIANCE WITH SECTION 11-4.15 AND ALL |
| SUBSECTIONS INCLUDING SECTION |
| 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO |
| HAVE DIFFICULTY BENDING OR STOOPING. |
| 5. SHT A-401 KITCHEN SINK SHALL COMPLY |
| WITH SECTION 11-4.24 AND ALL |
| SUBSECTIONS. PROVIDE A DETAIL SHOWING |
| COMPLIANCE. FORWARD APPROACH IS REQUIRED |
| FOR THE CLEAR FLOOR SPACE EXTENDING A |
| MAXIMUM OF 19" UNDERNEATH THE SINK. |
| CABINET DOORS ARE NOT ALLOWED IN CLEAR |
| FLOOR SPACE. |
| 6. P-401 FLOOR SINK OR HUB DRAIN IS |
| REQUIRED FOR THE ICE MACHINE. SECTION |
| 802.1 |
| 7. SHT P-401 FOUNTAIN AND FUTURE |
| FOUNTAIN WATER SUPPLY STUB OUT REQUIRE |
| BACKFLOW PROTECTION PER SECTION 608. |
| PLEASE INDICATE METHOD OF PROTECTION. |
| 8. SHT P-602 WATER RISER DIAGRAM, WATER |
| HAMMER ARRESTORS ARE REQUIRED AT THE ICE |
| MACHINES AND THE REFRIGERATOR WITH AN |
| ICE MAKER. SECTION 604.9. - THE WATER |
| HAMMER ARRESTORS AT THE KITCHEN SINK |
| SHALL BE LOCATED NEAR THE FIXTURES IN AN |
| "EFFECTIVE RANGE" NOT IN THE CEILING AS |
| SHOWN. PDI-WH 201 AND MANUF. INSTALL. |
| INSTRUCTIONS. |
| 9. SHT P602 BACKFLOW PROTECTION REQUIRED |
| FOR FOUNTAINS. (SEE COMMENT 7). |
| 10. THE FOLLOWING INFORMATION IS |
| REQUIRED FOR THE GAS PERMITS. (NATURAL |
| FOR THE STRUCTURE, AND LP FOR THE |
| GENERATOR): |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. - NOT ALL LENGTHS FOR |
| EACH SECTION SHOWN. |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE IF BEING USED. |
| - SUBMITTAL BOOK INDICATES VARIOUS |
| TYPES, BUT THE SPECIFIC MATERIAL SHALL |
| BE SHOWN ON THE PLANS FOR SIZING |
| PURPOSES. SECTION 402. |
| C. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). - TOTAL CONNECTED CAPACITY IS |
| INDICATED AS 698,000 CFH. PLEASE |
| CLARIFY. SECTION 106.1.1. |
| D. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). - ADDING UP |
| MEASUREMENTS SUBMITTED ON GAS RISER |
| DIAGRAM, THE TOTAL DEVELOPED LENGTH IS |
| CLOSE TO 200FT. PLEASE RECHECK LENGTH TO |
| THE MOST REMOTE OUTLET. |
| E. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| GAS CODE SECTION 304. - INDICATE CUBIC |
| FEET OF THE ROOM THE GAS DRYER IS IN TO |
| DETERMINE IF IT IS IN A CONFINED SPACE. |
| F. SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMINATION OF THE |
| GAS VENTS PER FBC-2004 FUEL GAS CODE |
| SECS. 502 THRU 506. |
| G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| H. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. - UNION NOT |
| APPROVED UPSTREAM OF MANUAL SHUT OFF |
| VALVE. IDENTIFY VALVE SHOWN UPSTREAM OF |
| THE MANUAL SHUT OFF VALVE AND UNION. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |