Plan Review Notes
Plan Review Notes For Permit 05110655
Permit Number 05110655
Review Stop P
Sequence Number 1
Notes
Date Text
2005-12-07 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL CODE
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS L100 THRU L700 AND IR100, IR500.
 THE CERTIFICATE OF AUTHORIZATION NUMBER
 FOR THE LANDSCAPE ARCHITECT BUSINESS IS
 REQUIRED IN THE TITLE BLOCK OF EACH
 SHEET. FAC 61G1-16.004(2). THE PRINTED
 NAME OF THE PERSON SEALING THE DOCUMENT
 IS REQUIRED ON EACH SHEET. FAC
 61G1-16.004(6). FS 481.319 & 481.2055
 2. A-105 EQUIPMENT ACCESSORIES SCHEDULE
 NUMBERS 43, 44, & 45. MORE INFORMATION
 IS REQUIRED. SUBMIT MANUF. SPECIFICATION
 SHEETS FOR THE COMPRESSOR, STORAGE, AND
 FILL STATION FOR THIS SYSTEM. SECTION
 106.1.2.
 3. SHT A-401 ACCESSIBLE TOILET ROOM
 DETAIL. THE FOLLOWING INFORMATION IS
 REQUIRED TO SHOW COMPLIANCE WITH CHAPTER
 11:
 FOR W/C'S:
 A. 11-4.16.3 HEIGHT
 B. 11-4.16.5 FLUSH CONTROLS
 C. W/C'S TO BE 18" OFF WALL TO CENTER
 OF FIXTURE. (FIG. 28)
 FOR LAVS:
 A. 11-4.19.2 CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 FOR SHOWERS:
 A. 11-4.21.2 SIZE AND CLEARNACES
 B. 11-4.21.3 SEAT
 C. 11-4.21.5 CONTROLS
 D. 11-4.21.6 SHOWER UNIT
 E. 11-4.21.7 CURBS
 4. PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS INCLUDING SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING.
 5. SHT A-401 KITCHEN SINK SHALL COMPLY
 WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. PROVIDE A DETAIL SHOWING
 COMPLIANCE. FORWARD APPROACH IS REQUIRED
 FOR THE CLEAR FLOOR SPACE EXTENDING A
 MAXIMUM OF 19" UNDERNEATH THE SINK.
 CABINET DOORS ARE NOT ALLOWED IN CLEAR
 FLOOR SPACE.
 6. P-401 FLOOR SINK OR HUB DRAIN IS
 REQUIRED FOR THE ICE MACHINE. SECTION
 802.1
 7. SHT P-401 FOUNTAIN AND FUTURE
 FOUNTAIN WATER SUPPLY STUB OUT REQUIRE
 BACKFLOW PROTECTION PER SECTION 608.
 PLEASE INDICATE METHOD OF PROTECTION.
 8. SHT P-602 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS ARE REQUIRED AT THE ICE
 MACHINES AND THE REFRIGERATOR WITH AN
 ICE MAKER. SECTION 604.9. - THE WATER
 HAMMER ARRESTORS AT THE KITCHEN SINK
 SHALL BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUF. INSTALL.
 INSTRUCTIONS.
 9. SHT P602 BACKFLOW PROTECTION REQUIRED
 FOR FOUNTAINS. (SEE COMMENT 7).
 10. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMITS. (NATURAL
 FOR THE STRUCTURE, AND LP FOR THE
 GENERATOR):
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - NOT ALL LENGTHS FOR
 EACH SECTION SHOWN.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 - SUBMITTAL BOOK INDICATES VARIOUS
 TYPES, BUT THE SPECIFIC MATERIAL SHALL
 BE SHOWN ON THE PLANS FOR SIZING
 PURPOSES. SECTION 402.
 C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). - TOTAL CONNECTED CAPACITY IS
 INDICATED AS 698,000 CFH. PLEASE
 CLARIFY. SECTION 106.1.1.
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - ADDING UP
 MEASUREMENTS SUBMITTED ON GAS RISER
 DIAGRAM, THE TOTAL DEVELOPED LENGTH IS
 CLOSE TO 200FT. PLEASE RECHECK LENGTH TO
 THE MOST REMOTE OUTLET.
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304. - INDICATE CUBIC
 FEET OF THE ROOM THE GAS DRYER IS IN TO
 DETERMINE IF IT IS IN A CONFINED SPACE.
 F. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 506.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 H. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. - UNION NOT
 APPROVED UPSTREAM OF MANUAL SHUT OFF
 VALVE. IDENTIFY VALVE SHOWN UPSTREAM OF
 THE MANUAL SHUT OFF VALVE AND UNION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS