2005-11-28 00:00:00 | DENIED:PLAN CHECK ONLY / 2004 FBC |
| 1.PLAN SHEET M-101 & M-601, EF-1 & 2 |
| LOCATED IN THE APPARATUS BAY.EQUIPMENT |
| SCHEDULE INDICATES THE FANS ARE |
| INTERLOCKED WITH THE BAY DOORS.PLEASE |
| CLARIFY VENTILATION WHEN THE GARAGE |
| DOORS ARE CLOSED. |
| |
| 2.O.A. CALCULATIONS WERE PROVIDED FOR |
| ALL AREAS EXCEPT THE APPARATUS BAY. |
| PLEASE PROVIDE CALCULATIONS IN |
| ACCORDANCE WITH 2004 FMC 404.2.PLEASE |
| NOTE, ADJOINING AREAS THAT CONNECT TO |
| THE APPARATUS BAY SHALL BE MAINTAINED AT |
| A POSITIVE PRESSURE PER 404.3. |
| |
| 3.PLEAES INDICATE IF THE CO SENSOR |
| WILL BE TIED INTO EF-1 & 2. |
| |
| 4.ADDITIONAL PERMITS REQUIRED FOR THE |
| HOOD & FIRE SUPPRESSION.PLEASE PROVIDE |
| MANUFACTURERS SUBMITTAL DATA & PLANS |
| WITH PERMIT APPLICATION.PLEASE |
| INDICATE CLEARANCES TO COMBUSTIBLES PER |
| 2004 FMC 506.3.7. |
| |
| 5.PLEASE PROVIDE MANUFACTURERS |
| SUBMITTAL DATA FOR THE GAS GRILL LOCATED |
| UNDER THE COVERED PATIO. |
| |
| 6.PLEASE CLARIFY CALCULATIONS FOR THE |
| DECONTAMINATION ROOM.DO THEY INCLUDE |
| COMBUSTION AIR? |
| |
| 7.PLAN SHEET E-100 INDICATES PROPANE |
| TANK & EMERGENCY GENERATOR.PLEASE |
| PROVIDE MANUFACTURE SUBMITTAL DATA. |
| PROVIDE CAPACITY OF THE PROPANE TANK. |
| INDICATE ABOVE GROUND OR UNDERGROUND |
| INSTALLATION.PROVIDE DISTANCES TO |
| PROPERTY LINES, BUILDINGS, ETC.SHOW |
| COMPLIANCE WITH NFPA 58-102. |
| |