2005-11-21 00:00:00 | ******PLAN REVIEW ONLY****** |
| DENIED |
| |
| 1) SEPARATE SHOP DRAWINGS AND PERMITS |
| ARE REQUIRED FOR FIRE SPRINKLER AND FIRE |
| ALARM SYSTEMS. |
| |
| 2) PLEASE INCLUDE CALCULATED MARGIN OF |
| SAFETY WITH FIRE SPRINKLER HYDRAULIC |
| ANALYSIS THAT IS CONSISTENT WITH |
| PROVIDED DATA. |
| |
| 3) SEPARATE SHOP DRAWINGS AND PERMIT |
| WITH MANUFACTURER SPEC SHEETS REQUIRED |
| FOR GENERATOR AND FUEL TANK. |
| |
| 4) LIFE SAFETY TO COMPLY WITH NFPA 101, |
| 2003 EDITION AFTER JAN. 1, 2005. |
| |
| 5) FIRE SPRINKLER HEADS IN LOBBY AND |
| ADJOINING AREAS APPEAR TO BE MISSING |
| FROM SOME SHEETS, HOWEVER SIDE WALL |
| SPRINKLERS ARE NOTED ON FIRE PROTECTION |
| SHEETS. |
| |
| 6) SEPARATE SHOP DRAWINGS AND PERMITS |
| ARE REQUIRED FOR HOOD AND FIRE |
| SUPPRESSION SYSTEMS. |
| |
| 7) ALL RATED DOORS SHALL HAVE UL LISTED |
| CLOSERS. PLEASE SHOW ON DOOR SCHEDULE. |
| |
| 8) FIRE ALARM SYSTEM TO BE CLASS A, |
| STYLE D OR FULLY ADDRESSABLE. |
| |
| 9) FIRE ALARM SYSTEM IS REQUIRED TO BE |
| UL CERTIFIED FOR CENTRAL STATION |
| SERVICE. |
| |
| 10) SHEET E-132, NOTE #17 STATES THAT |
| FIRE ALARM IS LOCAL. PLEASE MAKE |
| CORRECTION. |
| |
| 11) NFPA 72, 2002 EDITION SHALL BE |
| REFERENCED. |
| |
| 12) SHEET E-132, NOTE #19 IS INCORRECT. |
| BUILDING IS TO BE FIRE SPRINKLERED. |
| |
| 13) IN ACCORDANCE WITH LOCAL |
| REQUIREMENTS, DUCT SMOKE DETECTORS WHERE |
| PROVIDED SHALL INITIATE A GENERAL FIRE |
| ALARM CONDITION, NOT SUPERVISORY SIGNAL. |
| |
| 14) PLEASE PROVIDE MORE INFORMATION |
| REGARDING GATE CONTROLLER FAIL SAFE |
| OPERATION IN THE EVENT OF POWER FAILURE. |
| |
| |
| 15) IN ADDITION TO ELECTRONIC |
| SUPERVISION, DOUBLE CHECK DETECTOR |
| ASSEMBLY TO BE SECURED WITH LOCK AND |
| CHAIN. |
| |
| 16) ELECTRICAL SHEETS SHOW MANUAL PULL |
| STATIONS, AND SHEET E-132, NOTE #23 |
| STATES THAT THEY HAVE BEEN ELIMINATED. |
| PLEASE CORRULATE. |
| |
| 17) ALL CONSTRUCTION, ALTERATION AND |
| DEMOLITION TO COMPLY WITH NFPA 241. |
| |
| |
| MIKE WENNERGREN, CAPTAIN/WPBFR |
| FIRE PLAN REVIEW (561) 805-6722 |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |