 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE GROUNDING ELECTRODE SYSTEM MUST
 COMPLY WITH ARTICLE 250.50, EACH ITEM IN
 250.52(A)(1) THROUGH(A)(6) MUST BE USED.
 INDICATE WHICH ARE AVAILABLE ON THE
 RISER DIAGRAM THAT PRESENTLY ONLY SHOWS
 A GROUND ROD AND WATER PIPE. ALSO VERIFY
 THAT THE WATER PIPE IS METAL AND NOT
 PVC.
  
 2} THE #2 GROUNDING ELECTRODE CONDUCTOR
 IS NOT COMPLIANT PER 250.66. #1/0
 MINIMUM IS REQUIRED. SEE ARTICLE.
 CORELATE SHEET E-501 WHICH SHOW A 4/0
 DELTA GROUND.
  
 3} THE RISER INDICATES 3#500(ASSUME
 UNGROUNDED CONDUCTORS) AND A #2 GROUND
 FROM THE FIRST DISCONNECT TO THE ATS AND
 ON TO THE MDP. THE GROUNDED CONDUCTOR IS
 NOT SHOWN. ALSO TO THE MDP.
  
 4} THE GROUNDING SYMBOL AT THE GENERATOR
 INDICATE A GROUNDED NEUTRAL. IS THIS
 INTENDED TO OPERATE AS A SEPERATELY
 DERIVED SYSTEM? THE ATS DOES NOT
 INDICATE WHETHER IT IS A 3 OR 4 POLE.
  
 5} THE GENERATOR FEEDERS TO THE ATS DO
 NOT INDICATE A NEUTRAL. SAME COMMENT AS
 #3.
  
 6} PLEASE CHECK THE MANUFACTURERS
 NAMEPLATE RATING AGAINST THE500 MCM
 FEEDERS, SEE 445.13@115%.
  
 7} SUPPLY MANUFACTURERS SPECIFICATIONS
 FOR THE GENERATOR AND ATS.
  
 8} PLEASE PROVIDE A PANEL SCHEDULE FOR
 MDP AND DP1.
  
 9} PLEASE INDICATE THE CIRCUIT NUMBERS
 FOR THE EQUIPMENT AT THE EQUIPMENT
 LOCATION ON THE PLAN, SEE CU'S ON SHEET
 E-120, WH, OVERHEAD DOORS ETC.
  
 10} PLEASE COMPLY WITH 210.8(B)(3), SEE
 KITCHEN COUNTERTOPS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  