2005-11-29 00:00:00 | |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} THE GROUNDING ELECTRODE SYSTEM MUST |
| COMPLY WITH ARTICLE 250.50, EACH ITEM IN |
| 250.52(A)(1) THROUGH(A)(6) MUST BE USED. |
| INDICATE WHICH ARE AVAILABLE ON THE |
| RISER DIAGRAM THAT PRESENTLY ONLY SHOWS |
| A GROUND ROD AND WATER PIPE. ALSO VERIFY |
| THAT THE WATER PIPE IS METAL AND NOT |
| PVC. |
| |
| 2} THE #2 GROUNDING ELECTRODE CONDUCTOR |
| IS NOT COMPLIANT PER 250.66. #1/0 |
| MINIMUM IS REQUIRED. SEE ARTICLE. |
| CORELATE SHEET E-501 WHICH SHOW A 4/0 |
| DELTA GROUND. |
| |
| 3} THE RISER INDICATES 3#500(ASSUME |
| UNGROUNDED CONDUCTORS) AND A #2 GROUND |
| FROM THE FIRST DISCONNECT TO THE ATS AND |
| ON TO THE MDP. THE GROUNDED CONDUCTOR IS |
| NOT SHOWN. ALSO TO THE MDP. |
| |
| 4} THE GROUNDING SYMBOL AT THE GENERATOR |
| INDICATE A GROUNDED NEUTRAL. IS THIS |
| INTENDED TO OPERATE AS A SEPERATELY |
| DERIVED SYSTEM? THE ATS DOES NOT |
| INDICATE WHETHER IT IS A 3 OR 4 POLE. |
| |
| 5} THE GENERATOR FEEDERS TO THE ATS DO |
| NOT INDICATE A NEUTRAL. SAME COMMENT AS |
| #3. |
| |
| 6} PLEASE CHECK THE MANUFACTURERS |
| NAMEPLATE RATING AGAINST THE500 MCM |
| FEEDERS, SEE 445.13@115%. |
| |
| 7} SUPPLY MANUFACTURERS SPECIFICATIONS |
| FOR THE GENERATOR AND ATS. |
| |
| 8} PLEASE PROVIDE A PANEL SCHEDULE FOR |
| MDP AND DP1. |
| |
| 9} PLEASE INDICATE THE CIRCUIT NUMBERS |
| FOR THE EQUIPMENT AT THE EQUIPMENT |
| LOCATION ON THE PLAN, SEE CU'S ON SHEET |
| E-120, WH, OVERHEAD DOORS ETC. |
| |
| 10} PLEASE COMPLY WITH 210.8(B)(3), SEE |
| KITCHEN COUNTERTOPS. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW |
| 561/805-6718 |
| [email protected] |