2006-03-18 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 FROM PREVIOUS LISTS:
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.THE NOC PROVIDED
 IS EXPIRED; OVER 90 DAYS WITHOUT
 COMMENCING WORK.THIS COMMENT DOES NOT
 PREVENT YOUR PERMIT FROM BEING ISSUED,
 BUT WILL BE REQUIRED PRIOR TO PERMIT
 PICKUP.
  
 2.)ENGINEERING REQUIRED; DESIGN
 PRESSURES FOR BUILDINGS OVER 60FEET ARE
 REQUIRED TO BE DESIGNED USING ASCE7,
 FBC1609.1.1.DOCUMENTS PREPARED BY AN
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD
 ARE TO BE SIGNED SEALED ORIGINALS
 FAC61G15-23.002.
  
 THIS HAS BEEN REQUESTED ON EVERY REVIEW.
 ENGINEERING WAS IN THE LAST SUBMITTAL
 BUT IS NO LONGER IN THE PACKAGE.THE
 NOTE FROM THE CONTRACTOR THAT THE
 ENGINEER SAID THAT THE STATE OF FLORIDA
 DOES NOT REQUIRE ENGINEERING DUE TO THE
 ADVENT OF COMPUTER SOFTWAREAND FLORIDA
 STATE PRODUCT APPROVAL IS ACKNOWLEDGED.
 HOWEVER, DESIGN PRESSURES FOR A HIGH
 RISE MUST BE DETERMINED AND CERTIFIED BY
 AN ENGINEER.THERE IS A DIFFERENCE
 BETWEEN THE STATE OF FLORIDA'S
 REQUIREMENTS FOR STATE PRODUCT APPROVAL
 AND THE AHJ'S (IN THIS CASE, CITY OF
 WEST PALM BEACH'S) REQUIREMENTS FOR
 PERMITTING.
  
 PLEASE DO NOT SUBMIT THIS PACKAGE AGAIN
 WITHOUT THE REQUIRED DOCUMENTATIONS.
  
 3.)THE NEW PRODUCT APPROVAL FOR THE
 SGD HAS NOT BEEN REVIEWED AS DESIGN
 PRESSURES FOR THE BUILDING HAVE NOT BEEN
 DETERMINED.