2006-03-10 00:00:00******* PROVISO ** 3RD REVIEW ********
  
 1)NOTE: PLEASE SEE LOAD SHOWN ON PANEL
 "A"FOR PANEL "C" DOES NOT CORRELATE
 WITH ACTUAL LOAD INDICATED ON PANEL "C",
 PLEASE ADJUST.
  
 2)NOTE: PLEASE SEE RISER INDICATES 40
 CIRCUIT PANELS, AND PANEL SCHEDULES
 INDICATE THESE AS 42 CIRCUIT PANELS.
  
 3)NOTE: PLEASE SEE THE NEW ADDED PANEL
 "D" NOW ALSO INDICATES A NEW GAS POOL
 HEATER?? . PLEASE SEE PANEL "C" ALREADY
 INDICATES ONE GAS POOL HEATER. PLEASE
 ALSO SEE PLANS DO NOT INDICATE TWO GAS
 POOL HEATERS?
 PLEASE CORRELATE.
  
 ** PLEASE REVISE AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW ALONG WITH ANY
 OTHER REVISIONS BEFORE "ROUGH"
 ELECTRICAL INSPECTION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION , IF
 THERE ARE ANY QUESTIONS, PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  