Plan Review Notes For Permit 05110490 |
Permit Number |
05110490 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2006-03-10 00:00:00 | ******* PROVISO ** 3RD REVIEW ******** | | | | 1)NOTE: PLEASE SEE LOAD SHOWN ON PANEL | | "A"FOR PANEL "C" DOES NOT CORRELATE | | WITH ACTUAL LOAD INDICATED ON PANEL "C", | | PLEASE ADJUST. | | | | 2)NOTE: PLEASE SEE RISER INDICATES 40 | | CIRCUIT PANELS, AND PANEL SCHEDULES | | INDICATE THESE AS 42 CIRCUIT PANELS. | | | | 3)NOTE: PLEASE SEE THE NEW ADDED PANEL | | "D" NOW ALSO INDICATES A NEW GAS POOL | | HEATER?? . PLEASE SEE PANEL "C" ALREADY | | INDICATES ONE GAS POOL HEATER. PLEASE | | ALSO SEE PLANS DO NOT INDICATE TWO GAS | | POOL HEATERS? | | PLEASE CORRELATE. | | | | ** PLEASE REVISE AND SUBMIT THE ABOVE | | INFORMATION FOR REVIEW ALONG WITH ANY | | OTHER REVISIONS BEFORE "ROUGH" | | ELECTRICAL INSPECTION. | | | | PLEASE SUBMIT THE ABOVE INFORMATION , IF | | THERE ARE ANY QUESTIONS, PLEASE DO NOT | | HESITATE IN CONTACTING THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|