2006-01-30 00:00:00 | ******** UNSAT2ND REVIEW ********** |
| |
| PLEASE SEE SOME EXISTING NOTES AND SOME |
| NEW NOTES. |
| |
| |
| |
| 1)NOTE: OK |
| |
| 2)NOTE: OK |
| |
| 3)NOTE: OK, HOWEVER PLEASE NOW SEE POOL |
| HEATER IS BEING SHOWN AS GAS, YET SHOWS |
| 4KW LOAD AND SHOWS BEING CONTINUOUS?? |
| PREVIOUS PLANS CALLED FOR AN ELEC HEAT |
| PUMP. |
| |
| ** PLEASE INDICATE ALL CONTINUOUS |
| LOADS ON POOL PANEL AT 125%. |
| PLEASE ALSO SEE THIS WILL CHANGE LOAD |
| AND EXCEED RATING OF OCP AND FEEDERS TO |
| POOL PANEL. PLEASE ADJUST AS NEW OCP AND |
| FEEDERS WILL NEED TO BE INCREASED. |
| 215.5,230.42,215..3,90.8 |
| |
| 4)NOTE: OK |
| |
| 5)NOTE: OK |
| |
| 6)NOTE: OK |
| |
| 7)NOTE: OK, HOWEVER PLEASE SEE |
| DISCONNECTING NOTE FOR DETACHED GARAGE. |
| |
| 8)NOTE: OK |
| |
| 9)NOTE: OK |
| |
| 10)NOTE: OK, NOTED. |
| |
| 11)NOTE:OK/ NO, PLEASE SEE DISCONNECT |
| SWITCH(S) SHOULD BE SHOWN FOR GDO NOW |
| ADDED. |
| PLEASE SEE NOTE ADDED FOR GROUNDING, |
| SHOULD REFERENCE 250.32, HOWS 225.31 |
| WHICH IS THE DISCONNECT REQUIREMENT. |
| PLEASE SEE 250.32 WHICH REQUIRES A |
| GROUNDING ELECTRODE TO FOOTER STEEL MIN |
| . |
| |
| **PLEASE SEE THE DETACHED GARAGE |
| WOULD REQUIRE MEANS OF DISCONNECT AS |
| REQUIRED UNDER 225.31-225.36. |
| PLEASE SEE DISCONNECTING MEANS MAY BE A |
| TOGGLE SWITCH TYPE DEVICE IF MEETING THE |
| EXCEPTIONS. |
| |
| 12)NOTE: OK |
| |
| 13)NOTE: NO, PLEASE SEE PANEL "A" SHOWS |
| A 5KW HEAT, LOAD CALCULATIONS INDICATE |
| 65% AS 6500W?? |
| PLEASE ALSO SEE PANEL "B" SHOWS TWO |
| UNITS AS 10KW, HOWEVER 65% ON LOAD |
| CALCUALTIONS INDICATES 9750W?? |
| PLEASE SEE 655 OF 20KW ,, |
| PLEASE CORRELATE ALL KW LOADS |
| FOR AHU'S WITH KW RAITNGS SHOWN ON |
| MECHANICAL PLANS. PLEASE MAKE ANY |
| ADJUSTMENTS NEEDED FOR OCP, AWG, LOAD |
| CALCS ETC. |
| 215.5 |
| |
| NEW NOTES: |
| |
| 1)NOTE: PLEASE SEE POOL PANEL IS SHOWN |
| ON PLANS BEING FED FROM WHAT APPEARS TO |
| BE THE INSIDE PANEL "B", YET RISER SHOWS |
| THIS COMING FROM THE OUTSIDE MCB PANEL. |
| ?? |
| ** PLEASE CORRELATE RISER AND PANELS AS |
| PANEL SCHEDULES SHOWN INDICATE THESE AS |
| MCB PANELS WHICH ARE 40 CIRCUIT PANELS, |
| YET RISER SHOWS THE MCB PANELS AS 8-16? |
| PLEASE ALSO SEE RISER AS THESE PANELS DO |
| NOT SEEM TO CORRELATE. |
| ** PLEASE PROVIDE PANEL SCHEDULES FOR |
| OUTDOOR MCB PANELS IF THERE ARE CIRCUITS |
| COMING FROM THESE PANELS AS SHOWN. |
| ** PLEASE SEE 230.7, SERVICE ENTRANCE |
| CONDUCTORS MAY NOT BE IN THE SAME |
| RACEWAY/ENCLOSURE WITH THE |
| BRANCHCIRCUITS OR FEEDERS. |
| PLEASE REVISE RISER DIAGRAM AS MCB PANEL |
| "B" MAY NOT BED FED THORUGH MCB PANEL |
| "A". |
| |
| 2)NOTE: PLEASE SEE COPY OF FS |
| 553.80(2)(B) WITH RESPECT TO DESIGN |
| PROFESSIONALS AND REPEAT COMMENTS FOR |
| CODE COMPLIANCE. |
| |
| ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| FROM PLANS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. |
| ONE COPYOF OLD/VOIDED SHEETS SHOULD BE |
| SUBMITTED FOR REFERENCE. |
| |
| ** PLEASE SEE ANY OTHER POSSIBLE |
| COMMENTS FROM OTHER REVIEWS WHICH MAY |
| AFFECT ELECTRICAL PLANS. |
| |
| ** PLEASE SUBMIT THE ABOVE INFORMATION |
| FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| |