Plan Review Notes
Plan Review Notes For Permit 05110490
Permit Number 05110490
Review Stop E
Sequence Number 2
Notes
Date Text
2006-01-30 00:00:00******** UNSAT2ND REVIEW **********
  
 PLEASE SEE SOME EXISTING NOTES AND SOME
 NEW NOTES.
  
  
  
 1)NOTE: OK
  
 2)NOTE: OK
  
 3)NOTE: OK, HOWEVER PLEASE NOW SEE POOL
 HEATER IS BEING SHOWN AS GAS, YET SHOWS
 4KW LOAD AND SHOWS BEING CONTINUOUS??
 PREVIOUS PLANS CALLED FOR AN ELEC HEAT
 PUMP.
  
 ** PLEASE INDICATE ALL CONTINUOUS
 LOADS ON POOL PANEL AT 125%.
 PLEASE ALSO SEE THIS WILL CHANGE LOAD
 AND EXCEED RATING OF OCP AND FEEDERS TO
 POOL PANEL. PLEASE ADJUST AS NEW OCP AND
 FEEDERS WILL NEED TO BE INCREASED.
 215.5,230.42,215..3,90.8
  
 4)NOTE: OK
  
 5)NOTE: OK
  
 6)NOTE: OK
  
 7)NOTE: OK, HOWEVER PLEASE SEE
 DISCONNECTING NOTE FOR DETACHED GARAGE.
  
 8)NOTE: OK
  
 9)NOTE: OK
  
 10)NOTE: OK, NOTED.
  
 11)NOTE:OK/ NO, PLEASE SEE DISCONNECT
 SWITCH(S) SHOULD BE SHOWN FOR GDO NOW
 ADDED.
 PLEASE SEE NOTE ADDED FOR GROUNDING,
 SHOULD REFERENCE 250.32, HOWS 225.31
 WHICH IS THE DISCONNECT REQUIREMENT.
 PLEASE SEE 250.32 WHICH REQUIRES A
 GROUNDING ELECTRODE TO FOOTER STEEL MIN
 .
  
 **PLEASE SEE THE DETACHED GARAGE
 WOULD REQUIRE MEANS OF DISCONNECT AS
 REQUIRED UNDER 225.31-225.36.
 PLEASE SEE DISCONNECTING MEANS MAY BE A
 TOGGLE SWITCH TYPE DEVICE IF MEETING THE
 EXCEPTIONS.
  
 12)NOTE: OK
  
 13)NOTE: NO, PLEASE SEE PANEL "A" SHOWS
 A 5KW HEAT, LOAD CALCULATIONS INDICATE
 65% AS 6500W??
 PLEASE ALSO SEE PANEL "B" SHOWS TWO
 UNITS AS 10KW, HOWEVER 65% ON LOAD
 CALCUALTIONS INDICATES 9750W??
 PLEASE SEE 655 OF 20KW ,,
 PLEASE CORRELATE ALL KW LOADS
 FOR AHU'S WITH KW RAITNGS SHOWN ON
 MECHANICAL PLANS. PLEASE MAKE ANY
 ADJUSTMENTS NEEDED FOR OCP, AWG, LOAD
 CALCS ETC.
 215.5
  
 NEW NOTES:
  
 1)NOTE: PLEASE SEE POOL PANEL IS SHOWN
 ON PLANS BEING FED FROM WHAT APPEARS TO
 BE THE INSIDE PANEL "B", YET RISER SHOWS
 THIS COMING FROM THE OUTSIDE MCB PANEL.
 ??
 ** PLEASE CORRELATE RISER AND PANELS AS
 PANEL SCHEDULES SHOWN INDICATE THESE AS
 MCB PANELS WHICH ARE 40 CIRCUIT PANELS,
 YET RISER SHOWS THE MCB PANELS AS 8-16?
 PLEASE ALSO SEE RISER AS THESE PANELS DO
 NOT SEEM TO CORRELATE.
 ** PLEASE PROVIDE PANEL SCHEDULES FOR
 OUTDOOR MCB PANELS IF THERE ARE CIRCUITS
 COMING FROM THESE PANELS AS SHOWN.
 ** PLEASE SEE 230.7, SERVICE ENTRANCE
 CONDUCTORS MAY NOT BE IN THE SAME
 RACEWAY/ENCLOSURE WITH THE
 BRANCHCIRCUITS OR FEEDERS.
 PLEASE REVISE RISER DIAGRAM AS MCB PANEL
 "B" MAY NOT BED FED THORUGH MCB PANEL
 "A".
  
 2)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS AND REPEAT COMMENTS FOR
 CODE COMPLIANCE.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 FROM PLANS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING.
 ONE COPYOF OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE.
  
 ** PLEASE SEE ANY OTHER POSSIBLE
 COMMENTS FROM OTHER REVIEWS WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
  