2005-12-07 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE FORM
 600A-04 (2004), PER 2004 FBC 13-600.0
 ABC .
 2) FLOOR PLANS A-1 DO NOT MATCH MECH.
 FLOOR PLAN.
 3) PLEASE CHECK RETURN AIR GRILL FOR
 AHU #1, 30X18 APPEARS 100 SQUARE INCHES
 TO SMALL.
 4) NEED TO FILE NOTICE OF COMMENCEMENT.
 5) DRYER VENT TERMINATION NEEDS TO BE 4
 FT. MIN. FROM A/C CONDENSER UNITS.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.