2005-12-07 00:00:00 | *** DENIED *** | | 1) ENERGY CALCULATIONS NEED TO BE FORM | | 600A-04 (2004), PER 2004 FBC 13-600.0 | | ABC . | | 2) FLOOR PLANS A-1 DO NOT MATCH MECH. | | FLOOR PLAN. | | 3) PLEASE CHECK RETURN AIR GRILL FOR | | AHU #1, 30X18 APPEARS 100 SQUARE INCHES | | TO SMALL. | | 4) NEED TO FILE NOTICE OF COMMENCEMENT. | | 5) DRYER VENT TERMINATION NEEDS TO BE 4 | | FT. MIN. FROM A/C CONDENSER UNITS. | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | TOM GORDON 805-6729 OR PATTY KRAUSS | | 805-6719. |
|