2005-12-07 00:00:00 | ******** UNSAT ********** |
| |
| 1)NOTE: PLEASE SEE ELECTRICAL PLANS DO |
| NOT CORRELATE WITH BLDG PLANS/A-SHEETS. |
| PLEASE SEE THESE ARE TWO COMPLETELY |
| DIFERENT HOUSES. |
| PLEASE ADJUST. |
| PLEASE VERIFY WHAT APPEARS TO BE A |
| CLOSET OF SOME SORT IN WALK IN CLOSET OF |
| MASTER BEDRM AREA THAT APPEARS TO SHOW A |
| WATER HEATER?? |
| 215.5 |
| |
| 2)NOTE: PLEASE SEE MISSING EQUIPMENT |
| GROUNDING CONDUCTORS FROM MAINS TO SUB |
| PANEL(S) A AND B. |
| 250.110,250.122 |
| |
| 3)NOTE: PLEASE INDICATE ALL CONTINUOUS |
| LOADS ON POOL PANEL AT 125%. |
| PLEASE ALSO SEE THIS WILL CHANGE LOAD |
| AND EXCEED RATING OF OCP AND FEEDERS TO |
| POOL PANEL. PLEASE ADJUST AS NEW OCP AND |
| FEEDERS WILL NEED TO BE INCREASED. |
| 215.5,230.42,215..3,90.8 |
| |
| 4)NOTE: PLEASE SEE MISSING RECEPTS PER |
| 210.52. PLEASE SEE ONE SET OF PLANS HAVE |
| BEEN REDLINED WITH MANY OF THESE |
| LOCATIONS INDICATED. |
| |
| 5)NOTE: PLEASE SEE RECEPT MISSING PER |
| 210.52H FOR HALLWAY. 10' OR MORE OF |
| WALL. |
| |
| 6)NOTE: PLEASE SEE MISSING RECEPT PER |
| 210.52E, FRONT GFI. |
| |
| 7)NOTE: PLEASE CORRELATE THE # OF GDO |
| CIRCUITS ON PANEL SCHEDULE WITH THE |
| ACTUAL # NEEDED ON PLANS. PLEASE SEE |
| OTHER GARAGE. |
| PLEASE ALSO SEE PLANS DO NOT INDICATE |
| ANY RECEPTS AT THESE LOCATIONS. |
| 215.5, 430.24. TABLES). |
| |
| 8)NOTE: PLEASE SEE DISC'S FOR A/C CU |
| UNITS SHALL MEET 110.26 |
| |
| 9)NOTE: PLEASE SEE NFPA -72 11-8.3.5 |
| WHICH REQUIRES ALL SD'S TO BE INSTALLED |
| WITH-IN 12" OF A FLAT CEILING AREA. |
| PLEASE SEE "TRAY" CEILING AREA WOULD |
| REQUIRE TO THESE SD'S LOCATED AT THESE |
| AREAS IF HEY ARE 12" OR MORE HIGHER THAN |
| SURROUNDING CEILING AREA. SEE REDLINED |
| PLANS. |
| |
| 10)NOTE: PLEASE SEE 410.8 FOR TYPE OF |
| FIXTURE AND MIN CLEARENCES PERMITTED |
| ABOVE TUB/WHIRLPOOL. PLEASE PLACE NOTE |
| ON PLANS AS THIS IS SHOWN AS A "J-BOX" |
| FOR FUTURE. |
| |
| 11)NOTE: PLEASE SEE THE DETACHED GARAGE |
| WOULD REQUIRE MEANS OF DISCONNECT AS |
| REQUIRED UNDER 225.31-225.36. |
| PLEASE SEE DISCONNECTING MEANS MAY BE A |
| TOGGLE SWITCH TYPE DEVICE IF MEETING THE |
| EXCEPTIONS. |
| |
| 12)NOTE: PLEASE CORRELATE THE NUMBER OF |
| RECESSED LTS ON PANEL LOAD CALCULATIONS |
| WITH THE # OF FIXTURES ON PLANS. |
| 215.5,220.3B4 |
| |
| 13)NOTE: PLEASE CORRELATE ALL KW LOADS |
| FOR AHU'S WITH KW RAITNGS SHOWN ON |
| MECHANICAL PLANS. PLEASE MAKE ANY |
| ADJUSTMENTS NEEDED FOR OCP, AWG, LOAD |
| CALCS ETC. |
| 215.5 |
| |
| ** PLEASE KNOW, DEPENDING ON POSSIBLE |
| CHANGES IN "HOUSE PLANS" OR LAYOUT NOT |
| ALL COMMENTS MAY BE ON THIS REVIEW IF |
| THIS CHANGE OCCURS. |
| |
| ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| FROM PLANS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. |
| ONE COPYOF OLD/VOIDED SHEETS SHOULD BE |
| SUBMITTED FOR REFERENCE. |
| |
| ** PLEASE SEE ANY OTHER POSSIBLE |
| COMMENTS FROM OTHER REVIEWS WHICH MAY |
| AFFECT ELECTRICAL PLANS. |
| |
| ** PLEASE SUBMIT THE ABOVE INFORMATION |
| FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |