2005-12-07 00:00:00******** UNSAT **********
  
 1)NOTE: PLEASE SEE ELECTRICAL PLANS DO
 NOT CORRELATE WITH BLDG PLANS/A-SHEETS.
 PLEASE SEE THESE ARE TWO COMPLETELY
 DIFERENT HOUSES.
 PLEASE ADJUST.
 PLEASE VERIFY WHAT APPEARS TO BE A
 CLOSET OF SOME SORT IN WALK IN CLOSET OF
 MASTER BEDRM AREA THAT APPEARS TO SHOW A
 WATER HEATER??
 215.5
  
 2)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM MAINS TO SUB
 PANEL(S) A AND B.
 250.110,250.122
  
 3)NOTE: PLEASE INDICATE ALL CONTINUOUS
 LOADS ON POOL PANEL AT 125%.
 PLEASE ALSO SEE THIS WILL CHANGE LOAD
 AND EXCEED RATING OF OCP AND FEEDERS TO
 POOL PANEL. PLEASE ADJUST AS NEW OCP AND
 FEEDERS WILL NEED TO BE INCREASED.
 215.5,230.42,215..3,90.8
  
 4)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52. PLEASE SEE ONE SET OF PLANS HAVE
 BEEN REDLINED WITH MANY OF THESE
 LOCATIONS INDICATED.
  
 5)NOTE: PLEASE SEE RECEPT MISSING PER
 210.52H FOR HALLWAY. 10' OR MORE OF
 WALL.
  
 6)NOTE: PLEASE SEE MISSING RECEPT PER
 210.52E, FRONT GFI.
  
 7)NOTE: PLEASE CORRELATE THE # OF GDO
 CIRCUITS ON PANEL SCHEDULE WITH THE
 ACTUAL # NEEDED ON PLANS. PLEASE SEE
 OTHER GARAGE.
 PLEASE ALSO SEE PLANS DO NOT INDICATE
 ANY RECEPTS AT THESE LOCATIONS.
 215.5, 430.24. TABLES).
  
 8)NOTE: PLEASE SEE DISC'S FOR A/C CU
 UNITS SHALL MEET 110.26
  
 9)NOTE: PLEASE SEE NFPA -72 11-8.3.5
 WHICH REQUIRES ALL SD'S TO BE INSTALLED
 WITH-IN 12" OF A FLAT CEILING AREA.
 PLEASE SEE "TRAY" CEILING AREA WOULD
 REQUIRE TO THESE SD'S LOCATED AT THESE
 AREAS IF HEY ARE 12" OR MORE HIGHER THAN
 SURROUNDING CEILING AREA. SEE REDLINED
 PLANS.
  
 10)NOTE: PLEASE SEE 410.8 FOR TYPE OF
 FIXTURE AND MIN CLEARENCES PERMITTED
 ABOVE TUB/WHIRLPOOL. PLEASE PLACE NOTE
 ON PLANS AS THIS IS SHOWN AS A "J-BOX"
 FOR FUTURE.
  
 11)NOTE: PLEASE SEE THE DETACHED GARAGE
 WOULD REQUIRE MEANS OF DISCONNECT AS
 REQUIRED UNDER 225.31-225.36.
 PLEASE SEE DISCONNECTING MEANS MAY BE A
 TOGGLE SWITCH TYPE DEVICE IF MEETING THE
 EXCEPTIONS.
  
 12)NOTE: PLEASE CORRELATE THE NUMBER OF
 RECESSED LTS ON PANEL LOAD CALCULATIONS
 WITH THE # OF FIXTURES ON PLANS.
 215.5,220.3B4
  
 13)NOTE: PLEASE CORRELATE ALL KW LOADS
 FOR AHU'S WITH KW RAITNGS SHOWN ON
 MECHANICAL PLANS. PLEASE MAKE ANY
 ADJUSTMENTS NEEDED FOR OCP, AWG, LOAD
 CALCS ETC.
 215.5
  
 ** PLEASE KNOW, DEPENDING ON POSSIBLE
 CHANGES IN "HOUSE PLANS" OR LAYOUT NOT
 ALL COMMENTS MAY BE ON THIS REVIEW IF
 THIS CHANGE OCCURS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 FROM PLANS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING.
 ONE COPYOF OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE.
  
 ** PLEASE SEE ANY OTHER POSSIBLE
 COMMENTS FROM OTHER REVIEWS WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
  