Plan Review Notes
Plan Review Notes For Permit 05110472
Permit Number 05110472
Review Stop B
Sequence Number 1
Notes
Date Text
2005-11-15 00:00:00DENIED
  
 1) THE FLORIDA PRODUCT APPROVAL COVER
 SHEET FOR THE FIRESTONE MODIFIED ROOFING
 WAS NOT SUBMITTED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
 WWW.FLORIDABUILDING.ORG
  
 2) THE SBS SYSTEM THAT IS SPECIFIED IN
 THE FIRESTONE NOA HAS A MAXIMUM DESIGN
 PRESSURE OF -45 PSF WITH NO INCREASE
 ALLOWED FOR ENHANCED FASTENING PER
 LIMITATION #9. THIS DOES NOT MEET THE
 REQUIRED UPLIFT PRESSURES AT THE ROOF
 CORNERS OR EDGES (ZONES 2 & 3) FOR
 EXPOSURE B AND 140 MPH WIND SPEED.
  
 3) THE MAXIMUM DESIGN PRESSURE SPECIFIED
 IN THE MULE-HIDE PRODUCT APPROVAL OF -45
 PSF WITH LIMITATION #9 DOES NOT MEET THE
 REQUIRED UPLIFT PRESSURE.
  
 4) THE FLORIDA PRODUCT APPROVAL FOR THE
 MULE-HIDE PRODUCT HAS A STATUS OF
 VALIDATED AND HAS NOT YET BEEN APPROVED
 BY THE STATE.
  
 5) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714