2005-11-30 00:00:00 | DENIED |
| |
| |
| |
| 1) OWNER OR OWNERS AGENT SHALL SUBMIT A |
| NOTICE OF COMMENCEMENT BEFORE A PERMIT |
| CAN BE ISSUED. |
| |
| 2) THE NOA'S FOR PGT INDUSTRIES |
| HORIZONTAL SLIDERS ARE INCOMPLETE DUE TO |
| OFF CENTER PHOTOCOPIES. RE-SUBMIT CLEAR |
| COPIES |
| |
| 3) WHERE DOORS AND WINDOWS ARE ATTACHED |
| TO WOOD BUCKS AND THE ATTACHMENT METHOD |
| IS NOT SPECIFIED, THE ANCHORING |
| PERFOMANCE SHALL BE EQUAL TO OR GREATER |
| THAN THAT OF THE WINDOW OR DOOR |
| ASSEMBLIES ATTACHMENT AS DEMONSTRATED BY |
| ACCEPTED ENGINEERING PRACTICES. R613.6.1 |
| FBC. RES |
| |
| 4) SPECIFY THE PANEL GAUGE, MOUNTING |
| METHOD AND CONNECTION TYPE IN THE STORM |
| PANEL NOA'S |
| |
| 5) THE SINGLE HUNG WINDOWS SPECIFIED DO |
| NOT MEET THE EMERGENCY EGRESS FOR |
| MINIMUM HEIGHT OF CLEAR OPENING AS |
| SPECIFIED IN R310.1.2 OF FBC. RES. IF |
| USED IN A BEDROOM |
| |
| 6) PROVIDE A FLOOR PLAN FOR THE LOCATION |
| OF THE BEDROOM WINDOWS THAT SHALL MEET |
| THE EMERGENCY EGRESS REQUIREMENTS AS |
| ESCAPE AND RESCUE OPENINGS. |
| |
| 7) WINDOW OPENINGS THAT REQUIRE |
| STRUCTURAL CHANGES TO THE BUILDING WILL |
| NEED DRAWINGS TO BE SUBMITTED THAT ARE |
| SIGNED AND SEALED BY A DESIGN |
| PROFFESIONAL. |
| |
| 8) NOTE THAT THE JELD-WEN DOOR SPECIFIED |
| IN THE PRODUCT APPROVAL CAN HAVE |
| OPTIONAL SIDE LITES ATTACHED. IF USED |
| IMPACT PROTECTION IS REQUIRED. |
| |
| |