Plan Review Notes
Plan Review Notes For Permit 05110410
Permit Number 05110410
Review Stop B
Sequence Number 1
Notes
Date Text
2005-11-30 00:00:00DENIED
  
  
  
 1) OWNER OR OWNERS AGENT SHALL SUBMIT A
 NOTICE OF COMMENCEMENT BEFORE A PERMIT
 CAN BE ISSUED.
  
 2) THE NOA'S FOR PGT INDUSTRIES
 HORIZONTAL SLIDERS ARE INCOMPLETE DUE TO
 OFF CENTER PHOTOCOPIES. RE-SUBMIT CLEAR
 COPIES
  
 3) WHERE DOORS AND WINDOWS ARE ATTACHED
 TO WOOD BUCKS AND THE ATTACHMENT METHOD
 IS NOT SPECIFIED, THE ANCHORING
 PERFOMANCE SHALL BE EQUAL TO OR GREATER
 THAN THAT OF THE WINDOW OR DOOR
 ASSEMBLIES ATTACHMENT AS DEMONSTRATED BY
 ACCEPTED ENGINEERING PRACTICES. R613.6.1
 FBC. RES
  
 4) SPECIFY THE PANEL GAUGE, MOUNTING
 METHOD AND CONNECTION TYPE IN THE STORM
 PANEL NOA'S
  
 5) THE SINGLE HUNG WINDOWS SPECIFIED DO
 NOT MEET THE EMERGENCY EGRESS FOR
 MINIMUM HEIGHT OF CLEAR OPENING AS
 SPECIFIED IN R310.1.2 OF FBC. RES. IF
 USED IN A BEDROOM
  
 6) PROVIDE A FLOOR PLAN FOR THE LOCATION
 OF THE BEDROOM WINDOWS THAT SHALL MEET
 THE EMERGENCY EGRESS REQUIREMENTS AS
 ESCAPE AND RESCUE OPENINGS.
  
 7) WINDOW OPENINGS THAT REQUIRE
 STRUCTURAL CHANGES TO THE BUILDING WILL
 NEED DRAWINGS TO BE SUBMITTED THAT ARE
 SIGNED AND SEALED BY A DESIGN
 PROFFESIONAL.
  
 8) NOTE THAT THE JELD-WEN DOOR SPECIFIED
 IN THE PRODUCT APPROVAL CAN HAVE
 OPTIONAL SIDE LITES ATTACHED. IF USED
 IMPACT PROTECTION IS REQUIRED.
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 (561)805-6716