2005-12-09 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE CITY OF WEST PALM BEACH HAS
 ADOPTED A POLICY FOR GENERATORS THAT IS
 ATTACHED. THE LOAD CALCULATION MUST BE
 DERIVED FROM 220.31.
  
 2} PLEASE SUBMIT A SITE PLAN SHOWING THE
 LOCATION OF ALL SERVICE AND GENERATOR
 EQUIPMENT SO THAT COMPLIANCE WITH
 225.31-39 CAN BE DETERMINED.
  
 THE PERMIT VALUE MUST INCLUDE THE COST
 OF ALL LABOR AND MATERIAL IF APPLYING
 FOR A GEN RES PERMIT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  