2005-11-16 00:00:00MECH. PLAN REVIEW:
  
 1. RETURN AIR OUT OF OFFICES/CONFRENCES
 AREA REFLECT R/A THROUGH CEALING. RETURN
 AIR TO A.H.U. REFLECT SPACE RETURN.
 PLEASE CORRECT AND RESUBMIT.
  
 FLEX DUCT CONNECTION REFLECTED ON M-1 IS
 NOT CORRECT, INSULATION IS COMPRESSED
 THEAR BY LOOSING R-RATING .
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.