Plan Review Notes For Permit 05110319 |
Permit Number |
05110319 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-11-17 00:00:00 | ********* UNSAT ********** | | | | | | 1)NOTE: PLEASE CORRELATE NEW OCP FROM | | PANEL 8HB FOR NEW TRANSFORMER/ PANELS. | | PLEASE SEE PANEL SCHEDULE SHOWS 125A | | BRKR, HOWEVER NOTES TO THE RIGHT OF | | PANEL SCHEDULE MENTIONS A NEW 3-POLE | | 70A. | | | | 2)NOTE: | | | | 3)NOTE: PLEASE SHOW GROUNDING FOR | | TRANSFORMER PER 250.30 FOR SEPARATELY | | DERIVED SYSTEMS. | | PLEASE ALSO SEE 250.66 FOR SIZING. | | | | 4)NOTE: PLEASE SHOW LOCATIONS OF | | DISCONNECT AND TRANSFORMER. | | LOCATIONS COULD NOT BE LOCATED ON PLANS. | | PLEASE SEE 450.13B, 450.9 ETC. | | PLEASE ALSO SEE 110.26 FOR MIN | | CLEARENCES. (DISC ETC. | | | | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM | | OTHER REVIEWER(S) WHICH MAY AFFECT | | ELECTRICAL PLANS. | | | | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS | | AND ONLY INSERT NEW REVISED SHEETS INTO | | COMPLETED SETS FOR REVIEW AND STAMPING. | | ONE SET OF OLD VOIDED SHEETS SHOULD BE | | SUBMITTED FOR REFERENCE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE IN CONTACTING | | THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|