Plan Review Notes For Permit 05110315 |
Permit Number |
05110315 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-12-09 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | TO THE FBC2004 | | | | 1.)PROVIDE A COPY OF THE CONDO | | ASSOCIATION APPROVAL. | | | | 2.)THE NOC INDICATES THAT THE WINDOWS | | WILL BE NON IMPACT, BUT IMPACT PRODUCT | | APPROVALS WERE SUBMTTED. | | | | 3.)ENGINEERING IS TO BE SIGNED, SEALED | | AND DATED ORIGINALS FAC61G15-23.002. | | | | 4.)THE WINDOWS ON THE NOA DO NOT MEET | | THE DESIGN PRESSURE FOR ZONE 5 INDICATED | | ON THE ENGINEERING. | | | | 5.)THE SPEC SHEET PROVIDED IS FOR A | | DIFFERENT PRODUCT (WITH HIGHER | | PRESSURES) THAN THE NOA PROVIDED. | | | | 6.)PROVIDE WINDOW SIZES AND | | CONFIGURATION TO BE INSTALLED.A | | MULLION PRODUCT APPROVAL WAS SUBMITTED | | BUT CODE COMPLIANCE CANNOT BE DETERMINED | | WITHOUT WINDOW SIZES AND MULL SPAN | | LENGTH. |
|