2006-11-06 09:39:24PROVISO:
 PLANS DO NOT INDICATE RETURN AIR DUCTS NEW / EXISTING
 OR ANNOTATE THE CEILING AS A RETURN AIR PLENUM.PER
 2004 FMC 601.4, BALANCED RETURN REQUIRED. SHOULD THE
 CEILING AREA BE A RETURN AIR PLENUM, NO COMBUSTIBLES
 ALLOWED IN THE RETURN AIR PLENUM IN ACCORDANCE WITH
 2004 FMC 602.2.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].