Plan Review Notes For Permit 05110145
Permit Number 05110145
Review Stop P
Sequence Number 1
Notes
Date Text
2005-11-06 00:00:00PAUL SCHMITZ
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 DENIED
 1) FAC 64E-9 PUBLIC POOLS AND WATER
 FEATURES, REQIURE PALM BEACH COUNTY
 HEALTH DEPARTMENT PLAN REVIEW PRIOR TO
 WEST PALMM BEACH, CONSTRUCTION SERVICES
 PLAN REVIEW.
 CONTACT:
 DUTCH HOLLAND 561-355-3070 X 1134
  
 2) SEC 424.1.6.1 SANITARY FACILITIES.
 REQUIRED FIXTURES SHALL BE PROVIDED AS
 INDICATED ON TABLE 424.1.6.1
 SHOW THE EXISTING, AND REQUIRED
 FACILITIES FOR THE ADDITION OF THE
 SPOLASH FEATURE, AND HOW THIS WILL
 EFFECT THE DELETION OF OF EXISTING
 FIXTURES.
 3)SHT ASP-1 LEGEND "H" TO MUNICIPAL
 DRAIN.
 SEC 1002.5 SIZE OF FIXTURE TRAPS.
 NOT LESS THAN THE SIZE INDICATED ON TAB.
 709.1
 SEC 1002.6 BUILDING TRAPS.
 BUILDING DRAIN TRAPS SHALL BE PROVIDED
 WITH A CLEAN OUT AND RELIEF VENT
 END OF COMMENTS. QUESTIONS 561-805-6692