Plan Review Notes For Permit 05110145 |
Permit Number |
05110145 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-11-07 00:00:00 | **** UNSAT **** | | | | | | | | PLEASE KNOW PLANS, ARE COMING BACK FOR | | COMMENTS FROM OTHER REVIEWERS, PLEASE | | MAKE THE BELOW CORRECTIONS AT THIS TIME. | | | | 1)NOTE: PLEASE SEE 250.6,250.24 THERE IS | | NO EQUIPMENT GROUNDING CONDUCTOR TO BE | | INSTALLED UNTIL AFTER THE FRIST MEANS OF | | DISCONNECT. | | | | 2)NOTE: PLEASE SEE PLANS CALL FOR A | | CONNECTION TO CITY WATER, HOWEVER THERE | | IS NO CONNECTIONS SHOWN ON THE GROUNDING | | ELECTRODE SYSTEM FOR COLD WATER/ BOND | | ETC. PLEASE SEE 250.50,250.104 ETC. | | | | 3)NOTE: PLEASE SUBMIT THE SPECS, CUT | | SHEETS ON THE FOUNTAIN/ CONTROLLER. | | PLEASE BE SURE SPECS INCLUDE A LISTING | | BY A NRTL, NATIONALLY RECOGNIZED TESTING | | LABORTORY. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESIATE IN CONTACTING THIS | | OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|