2005-11-07 00:00:00**** UNSAT ****
  
  
  
 PLEASE KNOW PLANS, ARE COMING BACK FOR
 COMMENTS FROM OTHER REVIEWERS, PLEASE
 MAKE THE BELOW CORRECTIONS AT THIS TIME.
  
 1)NOTE: PLEASE SEE 250.6,250.24 THERE IS
 NO EQUIPMENT GROUNDING CONDUCTOR TO BE
 INSTALLED UNTIL AFTER THE FRIST MEANS OF
 DISCONNECT.
  
 2)NOTE: PLEASE SEE PLANS CALL FOR A
 CONNECTION TO CITY WATER, HOWEVER THERE
 IS NO CONNECTIONS SHOWN ON THE GROUNDING
 ELECTRODE SYSTEM FOR COLD WATER/ BOND
 ETC. PLEASE SEE 250.50,250.104 ETC.
  
 3)NOTE: PLEASE SUBMIT THE SPECS, CUT
 SHEETS ON THE FOUNTAIN/ CONTROLLER.
 PLEASE BE SURE SPECS INCLUDE A LISTING
 BY A NRTL, NATIONALLY RECOGNIZED TESTING
 LABORTORY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESIATE IN CONTACTING THIS
 OFFICE.
  