Plan Review Notes
Plan Review Notes For Permit 05110092
Permit Number 05110092
Review Stop B
Sequence Number 1
Notes
Date Text
2005-11-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05110092
 ADD: 3246 S DIXIE HWY
 CONT: NEIL O'NEAL JR ROOFING
 TEL: (561)656-4945
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 _X__ CONTRACTOR DID NOT PROVIDE THE MEAN
  
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 _X__ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.FLAT ROOF SYSTEMS ARE
 FOR NEW ROOFS. SBS SYSTEM IS TO BE USED
 FOR TILE UNDERLAYMENT SYSTEM.
  
 ___ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE ___ .
  
 ___ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 ___THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 __X__ GAF TIMBERLINE SELECT 40 MISSING
 THE FL COVERSHEET.PRODUCT APPROVALS
 SUBMITTED WITH PERMIT APPLICATION AFTER
 OCTOBER 1, 2003 ARE REQUIRED TO COMPLY
 WITH THE FLORIDA PRODUCT APPROVAL
 SYSTEM. FOR INFORMATION PLEASE SEE THE
 STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  