Plan Review Notes
Plan Review Notes For Permit 05101243
Permit Number 05101243
Review Stop M
Sequence Number 2
Notes
Date Text
2005-12-19 00:00:00AS PER 2004 FBC(M) 602.2.1, MATERIALS
 EXPOSED WITHIN PLENUMS SHALL BE NON -
 COMBUSTIBLE OR SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND SMOKE -
 DEVELOPED INDEX OF NOT MORE THAN 50 WHEN
 TESTED IN ACCORDANCE WITH ASTM E 84.