2005-11-23 00:00:00******DENIED******
  
 1) WILL THIS SPACE MEET THE OCCUPANT
 LOAD FACTOR REQUIREMENTS IN ACCORDANCE
 WITH NFPA 101, 2003 EDITION TABLE
 7.3.1.2 FOR BUSINESS USE?
  
 2) LIFE SAFETY SHEET SHOWS AN
 AUDIO/VISUAL DEVICE IN CONFERENCE ROOM
 AND SHT E-2.1 INDICATES STROBE ONLY.
 PLEASE CORRULATE.
  
 3) IN ADDITION TO FIRE SPRINKLER,
 SEPARATE SHOP DRAWINGS AND PERMIT WILL
 BE REQUIRED FOR FIRE ALARM REMODEL.
  
  