2005-11-22 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05101243
 ADD: 701 OKEECHOBEE BLVD
 CONT: THE WEITZ CO
 TEL: (561)951-2677
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS INDICATE 2 DOORWAYS THAT DO NOT
 MEET THE CRITERIA FOR MANEUVERING
 CLEARENCES 11-4.13.5 / FIGURE 25.
 A) LEFT SIDE OF PLAN THE DOOR THAT
 CONNNECTS THE 2 OFFICES TOGETHER.
 B) YOUTH ORCHESTRA IT APPEARS TO BE
 FIXED CABINETRY ACROSS FROM THE WALL
 THAT WILL NOT ALLOW FOR THE 60" FOR A
 FRONT APPROACH NOR IS THERE ENOUGH ROOM
 FOR A SIDE APPROACH.
  
 2) PLEASE PROVIDE THE FIRE TEST REPORT
 FOR THE WIRE GLASS FOR THE 3/4 HR RATED
 DOOR & WINDOW, 715.4/ TABLE 715.4.3.
  
 3) THE DOORS TO THE RATED CORRIDOR, ARE
 THERE DOOR SILLS OR DOES THE CARPET
 CONTINUE UNDER THE RATED DOOR? PLANS ARE
 NOT CLEAR ON THIS?
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  