2006-02-17 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2004 |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| TO THE FBC2004 |
| |
| FROM PREVIOUS LIST: |
| |
| 1.)A NOTICE OF COMMENCEMENT MUST BE |
| FILED WITH THE CLERK OF COURTS BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| THE NOC PROVIDED IS EXPIRED, OVER 90 |
| DAYS WITHOUT COMMENCING WORK |
| FS713.13(2). |
| |
| 2.)PROVIDE BUILDING MEAN ROOF HEIGHT. |
| DESIGN PRESSURES FOR BUILDINGS OVER |
| 60FEET ARE REQUIRED TO BE DESIGNED USING |
| ASCE7, FBC1609.1.1.DOCUMENTS PREPARED |
| BY AN ENGINEER AND SUBMITTED FOR PUBLIC |
| RECORD ARE TO BE SIGNED SEALED ORIGINALS |
| FAC61G15-23.002. |
| |
| THE SCHEDULE GIVES DESIGN PRESSURES OF |
| -13.5 AND -14.1, BUT -45 IS CIRCLED ON |
| SHEET 9 OF THE PRODUCT APPROVAL.DESIGN |
| PRESSURES ARE TO BE DETERMINED BY FBC |
| TABLE 1609.6B AND 1609.6D. |
| |
| 3.)ADDRESSED. |
| |
| 4.)COMPLETE THE ATTACHED INSTALLATION |
| SCHEDULE, OR PROVIDE REQUIRED |
| INFORMATION IN A SIMILAR FORMAT.SEE |
| ATTACHED POLICY. |
| |
| THE FORM WAS NOT FILLED OUT CORRECTLY |
| (ALL COLUMNS BLANKEXCEPT FOR DPS WHICH |
| ARE INCORRECT).NO ANCHOR SPACING |
| INDICATED ON PRODUCT APPROVAL.NOT |
| ENOUGH INFORMATION PROVIDED TO DETERMINE |
| CODE COMPLIANCE. |
| |