Plan Review Notes
Plan Review Notes For Permit 05101201
Permit Number 05101201
Review Stop B
Sequence Number 2
Notes
Date Text
2006-02-17 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 FROM PREVIOUS LIST:
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 THE NOC PROVIDED IS EXPIRED, OVER 90
 DAYS WITHOUT COMMENCING WORK
 FS713.13(2).
  
 2.)PROVIDE BUILDING MEAN ROOF HEIGHT.
 DESIGN PRESSURES FOR BUILDINGS OVER
 60FEET ARE REQUIRED TO BE DESIGNED USING
 ASCE7, FBC1609.1.1.DOCUMENTS PREPARED
 BY AN ENGINEER AND SUBMITTED FOR PUBLIC
 RECORD ARE TO BE SIGNED SEALED ORIGINALS
 FAC61G15-23.002.
  
 THE SCHEDULE GIVES DESIGN PRESSURES OF
 -13.5 AND -14.1, BUT -45 IS CIRCLED ON
 SHEET 9 OF THE PRODUCT APPROVAL.DESIGN
 PRESSURES ARE TO BE DETERMINED BY FBC
 TABLE 1609.6B AND 1609.6D.
  
 3.)ADDRESSED.
  
 4.)COMPLETE THE ATTACHED INSTALLATION
 SCHEDULE, OR PROVIDE REQUIRED
 INFORMATION IN A SIMILAR FORMAT.SEE
 ATTACHED POLICY.
  
 THE FORM WAS NOT FILLED OUT CORRECTLY
 (ALL COLUMNS BLANKEXCEPT FOR DPS WHICH
 ARE INCORRECT).NO ANCHOR SPACING
 INDICATED ON PRODUCT APPROVAL.NOT
 ENOUGH INFORMATION PROVIDED TO DETERMINE
 CODE COMPLIANCE.
  