Plan Review Notes For Permit 05101201
Permit Number 05101201
Review Stop B
Sequence Number 1
Notes
Date Text
2005-12-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)PROVIDE BUILDING MEAN ROOF HEIGHT.
 DESIGN PRESSURES FOR BUILDINGS OVER
 60FEET
 ARE REQUIRED TO BE DESIGNED USING ASCE7,
 FBC1609.1.1.DOCUMENTS PREPARED BY AN
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD
 ARE TO BE SIGNED SEALED ORIGINALS
 FAC61G15-23.002.
  
 3.)PROVIDE A COPY OF THE CONDO
 ASSOCIATION APPROVAL.
  
 4.)COMPLETE THE ATTACHED INSTALLATION
 SCHEDULE, OR PROVIDE REQUIRED
 INFORMATION IN A SIMILAR FORMAT.SEE
 ATTACHED POLICY.
  
  
  