 PROVISO
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW PRIOR TO CALLING INSPECTION.
  
  
 1} 445.13 AMPACITY OF CONDUCTORS.
 THE AMPACITY OF THE CONDUCTORS FROM THE
 GENERATOR TERMINALS TO THE FIRST
 DISTRIBUTION DEVICE(S) CONTAINING
 OVERCURRENT PROTECTION SHALL NOT BE LESS
 THAN 115 PERCENT OF THE NAMEPLATE
 CURRENT RATING OF THE GENERATOR.
  
 2} THE FEEDER FROM THE ATS TO THE
 "EMERGENCY" PANEL ALSO MUST COMPLY WITH
 310.15. THE OCP MUST BE DECREASED OR THE
 CONDUCTOR SIZE INCREASED.I FTHERE ARE
 ANY QUESTIONS PLEASE CALL.
  