Plan Review Notes For Permit 05101198 |
Permit Number |
05101198 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-01-26 00:00:00 | | | PROVISO | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW PRIOR TO CALLING INSPECTION. | | | | | | 1} 445.13 AMPACITY OF CONDUCTORS. | | THE AMPACITY OF THE CONDUCTORS FROM THE | | GENERATOR TERMINALS TO THE FIRST | | DISTRIBUTION DEVICE(S) CONTAINING | | OVERCURRENT PROTECTION SHALL NOT BE LESS | | THAN 115 PERCENT OF THE NAMEPLATE | | CURRENT RATING OF THE GENERATOR. | | | | 2} THE FEEDER FROM THE ATS TO THE | | "EMERGENCY" PANEL ALSO MUST COMPLY WITH | | 310.15. THE OCP MUST BE DECREASED OR THE | | CONDUCTOR SIZE INCREASED.I FTHERE ARE | | ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | |
|