Plan Review Notes
Plan Review Notes For Permit 05101140
Permit Number 05101140
Review Stop B
Sequence Number 2
Notes
Date Text
2006-04-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)YOU HAVE SUBMITTED TWO PRODUCT
 APPROVALS FOR PANELS.CLARIFY; ARE YOU
 INSTALLING TWO DIFFERENT TYPES OF
 PANELS?
  
 2.)THE INSTALLATION SCHEDULE STATES
 THAT YOU ARE INSTALLING FL#358, BUT THIS
 IS NOT ONE OF THE PRODUCT APPROVALS
 SUBMTITED.
  
 3.)TWO COPIES OF ALL DOCUMENTS
 REQUIRED.ONLY ONE FLOOR
 PLAN/INSTALLATION SCHEDULE WAS
 SUBMITTED.
  
 4.)YOU HAVE SPECIFIED 1" FASTENERS,
 BUT THERE IS A 7/8" EMBEDMENT
 REQUIREMENT.THIS LEAVES ONLY 1/8" FOR
 STUCCO.PLEASE ADDRESS.
  
 5.)IT IS NOT CLEAR HOW YOU HAVE
 ARRIVED AT THE DESIGN PRESSURES.FOR
 INSTANCE, OPENING 3 IS 18SF, SHOULD BE
 -47.3 EXPOSURE C, 19' MRF AS YOU HAVE
 DECLARED ON THE INSTALLATION SCHEDULE.
 SEE FBC TABLE 1609.6B, 1606.2D.PLEASE
 CONTACT ME IF YOU NEED ASSISTANCE.
  