Plan Review Notes For Permit 05101140 |
Permit Number |
05101140 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-04-06 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 | | EXISTING BUILDING CODE | | FBC*CITY OF WEST PALM BEACH | | AMENDMENTS TO THE FBC2004 | | | | 1.)YOU HAVE SUBMITTED TWO PRODUCT | | APPROVALS FOR PANELS.CLARIFY; ARE YOU | | INSTALLING TWO DIFFERENT TYPES OF | | PANELS? | | | | 2.)THE INSTALLATION SCHEDULE STATES | | THAT YOU ARE INSTALLING FL#358, BUT THIS | | IS NOT ONE OF THE PRODUCT APPROVALS | | SUBMTITED. | | | | 3.)TWO COPIES OF ALL DOCUMENTS | | REQUIRED.ONLY ONE FLOOR | | PLAN/INSTALLATION SCHEDULE WAS | | SUBMITTED. | | | | 4.)YOU HAVE SPECIFIED 1" FASTENERS, | | BUT THERE IS A 7/8" EMBEDMENT | | REQUIREMENT.THIS LEAVES ONLY 1/8" FOR | | STUCCO.PLEASE ADDRESS. | | | | 5.)IT IS NOT CLEAR HOW YOU HAVE | | ARRIVED AT THE DESIGN PRESSURES.FOR | | INSTANCE, OPENING 3 IS 18SF, SHOULD BE | | -47.3 EXPOSURE C, 19' MRF AS YOU HAVE | | DECLARED ON THE INSTALLATION SCHEDULE. | | SEE FBC TABLE 1609.6B, 1606.2D.PLEASE | | CONTACT ME IF YOU NEED ASSISTANCE. | | |
|