2005-12-03 00:00:00 | PAUL SCHMITZ |
| FBC2001 FUEL GAS CODEPLAN REVIEW |
| FBC 2001 PLUMBING CODEPLAN REVIEW |
| DENIED |
| (1) FAC 61G-15.23.002(2) |
| ENGINEERS CERTIFICATE OF AUTHORIZATION |
| DELIQUENT. |
| (2) RPZV BACKFLOW PREVENTER SHALL BE |
| INSTALLED AND INSPECTED PRIOR TO |
| STARTING WORK ON POOL. |
| SEPARATE PERMIT REQUIRED BY LICENSED |
| PUMBING CONTRACTOR. |
| (3) SEC 106.1.1 INFORMATION ON |
| CONSTRUCTION DOUCMENTS, PLANS AND |
| PRODUCT APPROVAL, REQUIRED. |
| MANFACTURE CUT SHEETS ON POOL HEATER. |
| |
| (4) SEPERATE PERMIT FOR GAS PIPING. |
| THE FOLLOWING INFORMATION IS REQUIRED |
| FOR THE GAS PERMIT: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| 3. TYPE OF GAS, (LP OR NATURAL) |
| |
| 4. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| |
| 5. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| . |
| 6. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| |
| END OF COMMENTS QUESTIONS 561-805-6692 |
| |
| |
| |