Plan Review Notes For Permit 05100933 |
Permit Number |
05100933 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-01-26 00:00:00 | DENIED 2ND TIME | | | | REFERENCE: FBC-2004 SWIMMING POOLS AND | | CITY AMENDMENTS TO FBC-2004 CHAPTER 1 | | ADMINISTRATION 106.1.3 | | | | 1. 106.1.3 QUALITY OF BUILDING PLANS. | | THE BUILDING OFFICIAL MAY ESTABLISH | | THROUGH DEPARTMENTAL POLICY, STANDARDS | | FOR PLANS AND SPECIFICATIONS,IN ORDER TO | | PROVIDE CONFORMITY TO ITS RECORD | | RETENTION PROGRAM. PAGE ONE SHOWS A | | CROSSED OUT 1" VENT CHANGED TO 1-1/2" | | VENT, ON SIGNED AND SEALED PRINTS FROM | | ENGINEER THIS CHANGE MUST BE DONE BY THE | | ENGINEER, INITIALED AND DATED BY | | ENGINEER. | | 2. ON PAGE 3 THE PIPING SCHEMATIC SHOWS | | A 1" VENT THIS NEEDS TO CHANGE AND | | CORRELATE WITH THE WITH THE 1-1/2" VENT. | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561)805-6730 | | FAX (561)805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561)805-6721 |
|