Plan Review Notes
Plan Review Notes For Permit 05100915
Permit Number 05100915
Review Stop E
Sequence Number 3
Notes
Date Text
2006-03-26 00:00:00THE SIZE OF THE TAP BOX 38 X 38 X 24
 HOW DOES THIS MEET THE REQUIREMENTS OF
 314.28(A2) 12 - 4" PIPES? PLEASE
 INDICATE CODE SECTION FOR SIZING?
  
 THE LISTING I ASKED FOR WAS A LISTING
 AGENCY SUCH AS "UL" "ETL" ??? 110.2
  
 WHO IS THE MANUFACTURER OF THE TAP
 BOX????? 110.3A CUT SHEETS!
  
 PLEASE INDICATE HOW LOAD SHEADING IS TO
 BE ACCOMPLISHED??? WHAT IS TO BE SHEADED
 THE WHOLE DISTRIBUTION TIED TO
 THOSE SWITCHES PLEASE INDICATED LOADS TO
 BE SHEAD. 215.2(A)
  
 IF TAP BOX IS NOT LISTED PLEASE HAVE
 SWITCH GEAR MANUFACTURER RE-LIST GEAR
 WITH TAP BOX INSERTED.
 110.3 (A)(B)
  
  
 ALSO IN NOTES BACK TO CITY PG.E0.5
 NOT ONE OF THE PAGES SUBMITTED.
  
 NOTES ON PAGE E5.1 DO NOT LIST TESTING/
 LISTING AGENCY OR MANUFACTURER!