2006-03-25 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 THE COMMENTS FROM THE PREVIOUS
 BUILDING/STRUCTURAL PLAN REVIEW DATED
 1/17/06 WERE NOT ADDRESSED.THE KAMM
 CONSULTING COMMENT RESPONSE LETTER DATED
 2/6/06 STATES THAT IT DOES NOT ADDRESS
 THE STRUCTURAL COMMENTS.THE STRUCTURAL
 ENGINEER'S SHEETS S-1 AND S-2, SUBMITTED
 FOR THIS LATEST REVIEW, WERE SIGNED AND
 SEALED ON 11/23/05 WHICH IS BEFORE THE
 DATE OF THE LAST REVIEW (1/17/06).THEY
 ARE THE SAME SHEETS REVIEWED LAST TIME
 AND FOUND TO BE MISSING INFORMATION AS
 STATED ON THE LAST REVIEW.ALSO, THE
 DOCUMENT "OUTSTANDING DEPARTMENT
 REVIEWS' HAND CARRIED TO THIS OFFICE BY
 MR MARTY BISHOP, LISTS AND ADDRESSES THE
 MECHANICAL COMMENTS UNDER THE INCORRECT
 HEADING OF BUILDING (STRUCTURAL).
 CONSEQUENTLY, THAT DOCUMENT ALSO DOES
 NOTHING TO ADDRESS THE BUILDING
 (STRUCTURAL) REVIEW COMMENTS.
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE PREVIOUS
 BUILDING (STRUCTURAL) PLAN REVIEW OF
 1/17/06:
  
 2) FBC 1603.1.4WIND DESIGN DATA.THIS
 COMMENT HAS NOT BEEN ADDRESSED.THE
 FUEL TANK AND IT'S COMPONENTS ARE
 EXTERIOR. THE LOUVER AND SCREEN, AND THE
 ALTERATIONS TO THE CONCRETE BLOCK
 MASONRY WALL AROUND THE LOUVER, ARE ALL
 EXTERIOR 'COMPONENTS AND CLADDING'.THE
 PLANS MUST STATE THE BASIC WIND SPEED,
 WIND IMPORTANCE FACTOR, WIND EXPOSURE
 CATEGORY, INTERNAL PRESSURE COEFFICIENT,
 AND EXTERIOR COMPONENT AND CLADDING
 DESIGN WIND PRESSURES.ADD THIS
 INFORMATION TO THE PLANS.THE PLANS
 HAVE BEEN SEARCHED AND SCOURED LOOKING
 FOR THIS CODE REQUIRED INFORMATION SO,
 IF THE INFORMATION IS SOMEWHERE ON THESE
 PLANS, PLEASE CALL OR EMAIL TO TELL ME
 WHERE.
  
 3) THE FOLLOWING COMMENT WAS IGNORED.
 THERE ARE NUMEROUS OLD 'VOID' SHEETS
 LEFT IN THE SUBMITTED PLAN SETS.PLEASE
 READ THE FOLLOWING TEXT CAREFULLY AND
 FOLLOW THE DIRECTIONS:TO EXPEDITE
 REVIEW OF A RESUBMITTAL WHICH REQUIRES
 NEW PLANS IN ORDER TO ADDRESS THE ABOVE
 COMMENTS, THE OLD SHEETS SHALL BE
 REMOVED AND THE NEW SHEETS INSERTED.
 ONE COPY OF EACH OLD SHEET SHOULD BE
 STAPLED/CLIPPED TO THE REMAINING OLD
 SHEETS, TO FORM A SET OF 'OLD/VOID
 SHEETS', FOR COMPARISON OF REVISIONS
 WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]