Plan Review Notes
Plan Review Notes For Permit 05100915
Permit Number 05100915
Review Stop M
Sequence Number 2
Notes
Date Text
2006-01-19 00:00:00DENIED:
 1.PLEASE SUBMIT PLANS FOR REVIEW AND
 APPROVAL TO THE DEPARTMENT OF
 ENVIRONMENTAL PROTECTION LOCATED AT;
 3323 BELVEDERE RD BUILDING #502,
 ATTENTION CHIP GREEN.TELEPHONE
 (561)233-2504.
  
 2.PER 2001 FMC 1301.2.1, MAXIMUM
 AMOUNT OF FUEL OIL STORAGE ALLOWED
 WITHOUT ADDITIONAL PROTECTION SHALL BE
 660 GALLONS.FUEL OIL STORAGE GREATER
 THAN 660 GALLONS SHALL COMPLY WITH NFPA.
  
 3.PLEASE PROVIDE ANCHORING DETAIL OR
 TIE DOWN FOR FUEL TANK.
  
 4.SHOW COMPLIANCE WITH 2001 FMC 301.14
 FOR REQUIREMENTS MANDATED BY THE FLOOD
 ZONE.PLEASE PROVIDE SLAB ELEVATION.
  
 5.PLAN SHEET M2.1, PLEASE CLARIFY
 TERMINATION OF EF1 INTO WHAT APPEARS TO
 BE ANOTHER "ENCLOSED" ROOM.PER 2001
 FMC 501.3, ALL MECHANICAL EXHAUST SHALL
 DISCHARGE TO THE OUTDOORS.
  
 6.PLAN SHEET M2.1, THE PRIMARY &
 EMERGENCY VENTS ARE WITHIN 10FT OF THE
 SHEET METAL HOOD.IS THIS AN INTAKE?
 PER 2001 FMC 401.5.1 INTAKE OPENINGS
 SHALL BE LOCATED A MINIMUM OF 10 FT FROM
 ANY HAZARDOUS CONTAMINANT.
  
 7.PLAN SHEET P0.1 INDICATES BOTH
 GENERATORS WILL HAVE THE OPTION OF BEING
 POWERED BY DIESEL FUEL OR NATURAL GAS.
 PLEASE PROVIDE COMBUSTION AIR
 CALCULATIONS FOR BOTH GENERATOR ROOMS.
  
 8.PLANS INDICATE THE EXISTING
 GENERATOR WILL NOW HAVE THE OPTION TO
 RUN WITH NATURAL GAS.PLEASE PROVIDE
 SUBMITTAL DATA FOR THE EXISTING
 GENERATOR.
  
 9.PLEASE CLARIFY INTAKE LOUVERS FOR
 OUTSIDE AIR FROM THE ENCLOSED GARAGE?
  
 10. PLEASE SPECIFY PIPING MATERIAL FOR
 THE FUEL OIL PIPING & METHOD OF
 INSTALLATION IN ACCORDANCE WITH 2001 FMC
 TABLE 1302.3 & 1303.1 RESPECTIVELY.
  
 11. PLEASE NOTE FUEL OIL PIPING SHALL BE
 TESTED IN ACCORDANCE WITH NFPA 31.
  
 12. PLEASE PROVIDE DETAIL FOR PIPE
 SUPPORTS PER 2001 FMC 305.PLEASE NOTE,
 CORROSION PROTECTION REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].