2006-01-18 00:00:00DENIED:
  
 1) THE TANK STORAGE SHALL COMPLY WITH
 NFPA 30, NFPA 80, NFPA 90A, AND NFPA 91.
  
 2) THE TANK STORAGE ROOM SHALL BE 2 HOUR
 FIRE RATED.
  
 3) THE TANK STORAGE ROOM SHALL BE FIRE
 SPRINKLER PROTECTED.
  
 4) THE EXHAUST SYSTEM SHALL BE INSTALL
 IN ACCORDANCE WITH THE PROVISIONS OF
 NFPA 91.
  
 5) IS THIS TANK STORAGE AREA SUBJECTED
 TO FLOODING, IF SO CERTAIN REQUIREMENTS
 MUST BE MET OF NFPA 30.
  
 6) EACH STORAGE TANK BUILDING AND EACH
 TANK WITHIN THE BUILDING SHALL BE
 ACCESSIBLE FROM AT LEAST TWO SIDES FOR
 FIREFIGHTING AND FIRE CONTROL.
  
 7) APPROPRIATE SIGNAGE MAY BE REQUIRED.
  
 8) PLEASE SEE OTHER REVIEW COMMENTS.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754