2006-01-18 00:00:00 | DENIED: | | | | 1) THE TANK STORAGE SHALL COMPLY WITH | | NFPA 30, NFPA 80, NFPA 90A, AND NFPA 91. | | | | 2) THE TANK STORAGE ROOM SHALL BE 2 HOUR | | FIRE RATED. | | | | 3) THE TANK STORAGE ROOM SHALL BE FIRE | | SPRINKLER PROTECTED. | | | | 4) THE EXHAUST SYSTEM SHALL BE INSTALL | | IN ACCORDANCE WITH THE PROVISIONS OF | | NFPA 91. | | | | 5) IS THIS TANK STORAGE AREA SUBJECTED | | TO FLOODING, IF SO CERTAIN REQUIREMENTS | | MUST BE MET OF NFPA 30. | | | | 6) EACH STORAGE TANK BUILDING AND EACH | | TANK WITHIN THE BUILDING SHALL BE | | ACCESSIBLE FROM AT LEAST TWO SIDES FOR | | FIREFIGHTING AND FIRE CONTROL. | | | | 7) APPROPRIATE SIGNAGE MAY BE REQUIRED. | | | | 8) PLEASE SEE OTHER REVIEW COMMENTS. | | | | | | NATE MCCRAY, ASSISTANT FIRE MARSHAL | | 561-804-4754 |
|