Plan Review Notes For Permit 05100915 |
Permit Number |
05100915 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-11-04 00:00:00 | SPEC BOOK SHOWS ON COVER 120/208 | | EQUIPMENT, BUT INSIDE BOOK UNDER | | TRANSFER SWITCHES THE VOLTAGES LISTED | | ARE 277/480. | | | | SPECS FOR GENERATOR SHOW 277/480V???? | | | | PAGE E0.1 LIGHTING FIXTUR SCHEDULE SHOWS | | 277 VOLT LIGHTING.PANEL SCHEDULE SHOWS | | 120/208 VOLTS. | | | | PAGE E5.1 SHOWS NEW TAP BOXES ON MAINS | | FOR TOWER PLEASE SIZE BOX ON DRAWINGS | | PER CODE. 314.28 | | | | ON FEEDER SCHEDULE FEEDERS NT-1A, | | NT-1B,NT-!, NT-2DO NOT SPECIFY TYPE OF | | MATERIALCOPPER OR ALUMINUM. | | | | PAGE E6.1 SWITCHBOARD G2A HAS A LOAD OF | | 564 KVA GENERATRO IS RATED FOR 500 KVA. | | | | SWITCHBOARD G1A SHOWS 277/480V ??? | | | | | | | | QUESTIONS CALL JAKE LEAHY 561-644-7291. | | |
|