Plan Review Notes For Permit 05100904 |
Permit Number |
05100904 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2007-07-13 09:47:27 | MECHANICAL REVISION | | *** DENIED *** | | 1) EDWARD J. KRANZ (ENGINEER) SEALED THE MECHANICAL | | PLANS ON FILE SO HE NEEDS TO SEAL THE REVISION. | | | | 2) ENERGY CALCULATIONS ON FILE ARE TAKING CREDIT FOR A | | HEAT RECOVERY UNIT THE REVISED MECHANICAL PLANS HAVE | | THE HEAT RECOVERY UNIT REMOVED, PLEASE CORRECT. | | | | 3) SHOW HOW THE RETURN AIR IS GETTING BACK TO AHU 1 AND | | 3 , IF LOUVER DOOR PLEASE SHOW ON MECHANICAL PLANS. | | | | 4) THE 8X4 SUPPLY AIR GRILL FOR BATHROOM #3 IS LOCATED | | IN BEDROOM #5 NOT IN THE BATHROOM, PLEASE CORRECT. | | | | 5) PERMIT #07050292 OR 06110063 ARE FOR THE SAME JOB | | ONE WILL NEED TO BE VOIDED. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|