Plan Review Notes For Permit 05100904 |
Permit Number |
05100904 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2007-08-01 11:17:03 | | | | | REVISION DENIED/INCOMPLETE INFORMATION | | | | | | 1} PROVIDE A PANEL SCHEDULE FOR ADDED PANEL "C". | | | | 2} PANEL "C" IS NOT ON THE RISER DIAGRAM, PLEASE ADD | | SAME. | | | | 3} THE CONDENSER LABELED AC #3 IS IN BOTH PANEL "A" AND | | "EM", AND THE LOAD IN EACH IS DIFFERENT. PLEASE CORRECT | | TO SHOW ACTUAL CONDITIONS. | | | | 4} LOCATE THE DISCONNECT FOR AC #3, 440.14. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|