Date |
Text |
2006-02-21 00:00:00 | *** DENIED *** |
| 1) ENERGY CALCULATIONS NEED TO BE ON |
| FORM 600A-04 (2004) PER FBC 13-600.3.A . |
| |
| 2) AHU #1 RETURN AIR GRILL 30X14 IS TO |
| SMALL FOR A 5 TON A/C UNIT. NOTE, |
| KITCHEN DOOR WILL BLOCKRETURN AIR |
| GRILL IF LEFT OPEN. |
| |
| 3) CLOTHES DRYER NEEDS TO TERMINATE AT |
| LEAST 4 FEET FROM A/C CONDENSER UNIT. |
| |
| 4) COMBUSTION AIR INLETS TO LAUNDRY ROOM |
| CAN NOT HAVE GENERATOR EXHAUST, CLOTHES |
| DRYER VENT, A/C CONDENSER FAN WITHIN 10 |
| FEET, PER 2004 FBC/M 401.5.1 . |
| |
| 5) GENERATOR EXHUST MUST BE TEN FEET |
| AWAY FROM ANY BUILDING OPENINGS |
| (WINDOWS, DOORS, ROOF & EAVE VENTS), AND |
| TEN FEET AWAY FROM ADJECENT BUILDING |
| OPENS. PER 2004 FBC/M 401.5.1 . |
| |
| 6) DUCT (FLEX) TO BEDROOM #4 IS NOT |
| SIZED. |
| |
| 7) RETURN AIR GRILL 24X24 IS TO SMALL |
| FOR A 4 TON A/C UNIT. |
| |
| 8) NOTE, RETURN AIR TRANSFER DUCTS. |
| BALANCED RETURN AIR. |
| THIS MAY BE ACHIEVED BY. |
| (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| INCREASING THE RETURN TRANSFER ONE AND |
| ONE HALF TIMES THE CROSS SECTIONAL AREA |
| (SQUARE INCHES) OF THE SUPPLY DUCT |
| ENTERING THE ROOM OR SPACE IT'S SERVING |
| AND THE DOOR HAVING AT LEAST AN |
| UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| PROPER RETURN AIR BALANCE. |
| (B)TRANSFER GRILLES SHALL USE 50 |
| SQUARE INCHES (OF GRILLE AREA) TO 100 |
| CFM (OF SUPPLY AIR) FOR SIZING |
| THROUGH-THE-WALL TRANSFER GRILLES AND |
| USING AN UNRESTRICTED 1-INCH |
| UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| RETURN AIR BALANCE |
| (C)HABITABLE ROOMS ONLY SHALL BE |
| REQUIRED TO MEET THESE REQUIREMENTS FOR |
| PROPER BALANCED RETURN AIR EXCLUDING |
| BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| AIR INTO THE MASTER SUITE SHALL BE |
| INCLUDED. PER 2004 FBC/R M1602.4 . |
| |
| 8) PLEASE REMOVE ALL OLD PLANS FROM PLAN |
| SET. |
| |
| MECHANICAL PLAN REVIEW BY; |
| TOM GORDON (561) 805-6729. |
| |