2006-02-22 00:00:00DENIED;
 1.GAS RISER DIAGRAM DOES NOT SHOW POOL
 HEATER OR GENERATOR.
 2.NO SPECIFICATIONS WERE FOUND FOR
 INSTANT HOT. I COULD NOT FIND TOTLE
 BTU'S FOR STOVE AND DRIER FROM SPEC.
 SHEETS.
 3.BTU'S ON RISER DIAGRAM DO NOT MATCH
 BTU'S ON SPEC. SHEETS. (MARKED IN RED ON
 ONE SET OF PLANS)
 4.PIPE SIZES ARE NOT CORRECT, SEE
 FBC-2004 FUEL GAS TABLE 402.4(2).
 5.OTHER PIPING MATERIAL WILL BE USED BY
 THE GAS CONTRACTOR @ PE FOR UNDER
 GROUND, CSST IN ATTIC. EACH PIPING
 MATERIAL HAS IT'S OWN TABLE.
 IF YOU DELETE THE GAS RISER FROM YOUR
 PLAN THE GAS CONTRACTOR HIRED COULD
 PROVIDE THE REQUIRED DRAWINGS WITH THE
 GAS PERMIT APPLICATION AT A LATER TIME.