Plan Review Notes For Permit 05100904 |
Permit Number |
05100904 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-02-22 00:00:00 | DENIED; | | 1.GAS RISER DIAGRAM DOES NOT SHOW POOL | | HEATER OR GENERATOR. | | 2.NO SPECIFICATIONS WERE FOUND FOR | | INSTANT HOT. I COULD NOT FIND TOTLE | | BTU'S FOR STOVE AND DRIER FROM SPEC. | | SHEETS. | | 3.BTU'S ON RISER DIAGRAM DO NOT MATCH | | BTU'S ON SPEC. SHEETS. (MARKED IN RED ON | | ONE SET OF PLANS) | | 4.PIPE SIZES ARE NOT CORRECT, SEE | | FBC-2004 FUEL GAS TABLE 402.4(2). | | 5.OTHER PIPING MATERIAL WILL BE USED BY | | THE GAS CONTRACTOR @ PE FOR UNDER | | GROUND, CSST IN ATTIC. EACH PIPING | | MATERIAL HAS IT'S OWN TABLE. | | IF YOU DELETE THE GAS RISER FROM YOUR | | PLAN THE GAS CONTRACTOR HIRED COULD | | PROVIDE THE REQUIRED DRAWINGS WITH THE | | GAS PERMIT APPLICATION AT A LATER TIME. | | GAS PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|