 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT THE MANUFACTURERS
 SPECIFICATIONS FOR THE GEN SET AND ALL
 RELATED EQUIPMENT. NOTE THE TRANSFER
 SWITCH MUST BE SERVICE RATED PER 225.36.
 ALL ARTICLE 225 APPLIES TO THE
 GENERATOR, AS WELL AS 445, 700 & 702.
 THIS COMMENT WAS MEDE ON THE PREVIOUS
 REVIEW.
  
 2} THE CALCULATION FOR THE "EM" PANEL IS
 NOT PER ANY RECOGNIZED FORMULAS IN THE
 NEC. THERE IS NO CALC FOR 1WATT PER
 SQUARE FOOT. IT WAS INDICATING THAT HEAT
 WOULD NOT BE USED WITH EMERGENCY POWER.
 INDICATE HOW THE A/C WOULD BE EXCLUDED
 (LOCKED OUT) WHEN THE GENERATOR POWERS
 UP. IT WOULD APPEAR THAT WITH AN
 AUTOMATIC TRANSFER SWITCH OPERATION ALL
 BRANCH CIRCUITS IN THE "EM" PANEL WOULD
 BE ENERGIZED. SUGGEST REMOVING ALL LOADS
 FROM THAT PANEL NOT INTENDED TO BE
 ENERGIZED BY THE GEN SET.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  