Plan Review Notes For Permit 05100904 |
Permit Number |
05100904 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-02-21 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE SUBMIT THE MANUFACTURERS | | SPECIFICATIONS FOR THE GEN SET AND ALL | | RELATED EQUIPMENT. NOTE THE TRANSFER | | SWITCH MUST BE SERVICE RATED PER 225.36. | | ALL ARTICLE 225 APPLIES TO THE | | GENERATOR, AS WELL AS 445, 700 & 702. | | THIS COMMENT WAS MEDE ON THE PREVIOUS | | REVIEW. | | | | 2} THE CALCULATION FOR THE "EM" PANEL IS | | NOT PER ANY RECOGNIZED FORMULAS IN THE | | NEC. THERE IS NO CALC FOR 1WATT PER | | SQUARE FOOT. IT WAS INDICATING THAT HEAT | | WOULD NOT BE USED WITH EMERGENCY POWER. | | INDICATE HOW THE A/C WOULD BE EXCLUDED | | (LOCKED OUT) WHEN THE GENERATOR POWERS | | UP. IT WOULD APPEAR THAT WITH AN | | AUTOMATIC TRANSFER SWITCH OPERATION ALL | | BRANCH CIRCUITS IN THE "EM" PANEL WOULD | | BE ENERGIZED. SUGGEST REMOVING ALL LOADS | | FROM THAT PANEL NOT INTENDED TO BE | | ENERGIZED BY THE GEN SET. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | | | |
|