2005-11-14 00:00:00 | MECHANICAL PERMIT NOT BEING APPLIED FOR |
| AT THIS TIME. PLEASE NOTE THE FOLLOWING |
| REGUARDING YOUR MECHANICAL PLANS. |
| AHU #1 ( 1ST. FLOOR ) |
| 1) NEED TO SHOW RETURN AIR DUCT SIZE. |
| 2) TRANSFER DUCT IN STUDY MUST BE 1 1/2 |
| TIMES LARGER THAN SUPPLY AIR DUCT (8" |
| SUPPLY AIR DUCT REQUIRES A 10" RETURN |
| AIR TRANSFER DUCT). PER 2004 FBC/R |
| M1602.4 . |
| 3)RAG IN MASTER VESTIBULE IS TO SMALL, |
| TRANSFER GRILLS MUST BE 50 SQ. IN. PER |
| 100 CFM'S (300 SQ. IN.). PER FBC/R |
| M1602.4 . |
| 4) COMBUSTION AIR LOUVERS, PLEASE SEE |
| 2004 FBC/R M1701.5 . |
| 5) WILL NEED DETAILED MANUFACTURE'S |
| SPECIFICATION'S ON GAS FIREPLACE AND |
| COMBUSTION AIR CALCULATIONS. |
| 6) WILL NEED DETAILED MANUFACTURE'S |
| SPECIFICATION'S ON GAS BBQ UNDER COVERED |
| LOGGIA, OR AN APPROVED HOOD. |
| 7) PLANS CALL FOR 109,400 TOTAL BTU'S |
| ENERGY CALCULATIONS CALL FOR 68,000 |
| BTU,S THE TO MUST COINCIDE. |
| 8) PLEASE ADDRESS GENERATOR EXHUST. |
| 9) WILL NEED DETAILED MANUFACTURE'S |
| SPECIFICATION'S AND INSTALLATION |
| INSTRUCTIONS ON GENERATOR. |
| AHU #2 (2ND. FLOOR) |
| 10) RAG IN BEDROOM #5 NOT SIZED. |
| 11) TRANSFER DUCT IN BEDROOM #3 & 4 NEED |
| TO BE 10" . |
| 12) TRANSFER DUCT IN BEDROOM # 2 NOT |
| SIZED. |
| 13) RETURN AIR DUCT FROM 24X24 RAG TO |
| AHU #2 NOT SIZED. |