2005-11-19 00:00:00GAS PLAN DENIED.
 1.GAS PIPE SIZING IS NOT CORRECT
 FBC-2004 FUEL GAS TABLE 402.4(2)
 2.GALV PIPE UNDER GROUND MUST BE FACTORY
 RAPPED AND CAN NOT HAVE ANY EXPOSED
 AREAS. SEC. 404.8.
 3.PROVIDE MANUFATURE'S CUT SHEETS
 SHOWING BTU'S FOR EACH APPLIANCE.