Plan Review Notes For Permit 05100904 |
Permit Number |
05100904 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-11-19 00:00:00 | GAS PLAN DENIED. | | 1.GAS PIPE SIZING IS NOT CORRECT | | FBC-2004 FUEL GAS TABLE 402.4(2) | | 2.GALV PIPE UNDER GROUND MUST BE FACTORY | | RAPPED AND CAN NOT HAVE ANY EXPOSED | | AREAS. SEC. 404.8. | | 3.PROVIDE MANUFATURE'S CUT SHEETS | | SHOWING BTU'S FOR EACH APPLIANCE. | | GAS PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|