Plan Review Notes
Plan Review Notes For Permit 05100904
Permit Number 05100904
Review Stop E
Sequence Number 1
Notes
Date Text
2005-11-09 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT THE MANUFACTURERS
 SPECIFICATIONS FOR THE GEN SET AND ALL
 RELATED EQUIPMENT. NOTE THE TRANSFER
 SWITCH MUST BE SERVICE RATED PER 225.36.
 ALL ARTICLE 225 APPLIES TO THE
 GENERATOR, AS WELL AS 445, 700 & 702.
  
 2} THE FEEDER FROM THE GENERATOR MUST BE
 115% OF THE NAMEPLATE PER 445.13.
  
 3} THE GROUNDING ELECTRODE SYSTEM MUST
 BE ATTACHED AT THE METER OR THE FIRST
 MEANS OF DISCONNECT, IT MUST BE REMOVED
 FROM THE ATS. THE ATS SHOULD BE BONDED
 WITH THE EQUIPMENT GROUNDING CONDUCTOR,
 UNLESS THE GENERATOR IS A SEPERATLY
 DERIVED SYSTEM.
  
 4} PLEASE PROVIDE A LOAD SUMMARY FOR THE
 EMERGENCY LOAD.
  
 5} THE DINING ROOM RECEPTACLES MUST
 COMPLY WITH 210.52(B)(1 & 2), NO OTHER
 OUTLETS, SEE GALLERY AND FOYER.
  
 6}THE GFI'S IN THE MASTER BATH ARE SHOWN
 ON INCORRECT CIRCUITS. ONE IS SHOWN ON
 "C 17" (NO SUCH PANEL ON THE PLAN), THE
 OTHER ON "EM 7". PLEASE SEE 210.11(C(3).
  
 7} PLEASE SEE THE CIRCUIT FOR THE FAMILY
 ROOMEXTENDS TO A RECEPTACLE IN THE
 BREAKFAST ROOM. 210.52(B).
  
 8} PLEASE SEE BATH GFI IN THE CABANA IS
 INDICATED ON THE POOL PUMP CIRCUIT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved