Date |
Text |
2005-11-09 00:00:00 | |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} PLEASE SUBMIT THE MANUFACTURERS |
| SPECIFICATIONS FOR THE GEN SET AND ALL |
| RELATED EQUIPMENT. NOTE THE TRANSFER |
| SWITCH MUST BE SERVICE RATED PER 225.36. |
| ALL ARTICLE 225 APPLIES TO THE |
| GENERATOR, AS WELL AS 445, 700 & 702. |
| |
| 2} THE FEEDER FROM THE GENERATOR MUST BE |
| 115% OF THE NAMEPLATE PER 445.13. |
| |
| 3} THE GROUNDING ELECTRODE SYSTEM MUST |
| BE ATTACHED AT THE METER OR THE FIRST |
| MEANS OF DISCONNECT, IT MUST BE REMOVED |
| FROM THE ATS. THE ATS SHOULD BE BONDED |
| WITH THE EQUIPMENT GROUNDING CONDUCTOR, |
| UNLESS THE GENERATOR IS A SEPERATLY |
| DERIVED SYSTEM. |
| |
| 4} PLEASE PROVIDE A LOAD SUMMARY FOR THE |
| EMERGENCY LOAD. |
| |
| 5} THE DINING ROOM RECEPTACLES MUST |
| COMPLY WITH 210.52(B)(1 & 2), NO OTHER |
| OUTLETS, SEE GALLERY AND FOYER. |
| |
| 6}THE GFI'S IN THE MASTER BATH ARE SHOWN |
| ON INCORRECT CIRCUITS. ONE IS SHOWN ON |
| "C 17" (NO SUCH PANEL ON THE PLAN), THE |
| OTHER ON "EM 7". PLEASE SEE 210.11(C(3). |
| |
| 7} PLEASE SEE THE CIRCUIT FOR THE FAMILY |
| ROOMEXTENDS TO A RECEPTACLE IN THE |
| BREAKFAST ROOM. 210.52(B). |
| |
| 8} PLEASE SEE BATH GFI IN THE CABANA IS |
| INDICATED ON THE POOL PUMP CIRCUIT. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW |
| 561/805-6718 |
| [email protected] |
| FAX/:561/659-8026 |
| |
| |
| |
| |