2005-12-23 00:00:00 | DENIED |
| 1. 713.13(2) F.S.THE NOTICE OF |
| COMMENCEMENT MUST BE RE-RECORDED BECAUSE |
| THE DESCRIBED IMPROVEMENT OR |
| CONSTRUCTION DID NOT COMMENCE WITHIN 90 |
| DAYS OF RECORDING. |
| |
| 2.SUBMIT TWO ORIGONAL SIGNED AND |
| SEALED SURVEYS. |
| |
| 3.ALL PLANS SUBMITTED AFTER OCTOBER 1, |
| 2005 SHALL BE DESIGNED TO THE 2004 FBC. |
| |
| 4.SUBMIT ENERGY CALCS TO THE 2004 FBC. |
| |
| 5.ENERGY CALCS DO NOT MATCH R- VALUES |
| ON PLANS. |
| |
| 6.SUBMIT SPECS FOR HOOD AND GAS BBQ. |
| A HOOD IS REQUIRED FOR BUILT IN UNITS. |
| |
| 7.SUBMIT GUARD RAIL DETAILS PER |
| R-312.1 |
| |
| 8.SUBMIT PRODUCT APPROVAL FOR BITUMEN |
| ROOF WITH THE FOLLOWING STATE PRODUCT |
| APPROVAL ATTACHED. |
| PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 9.PLEASE CLARIFY... IS THE ULTIMATE |
| DOOR TO BE USED IN THE FRONT ENTRY? |
| IF IT IS A DIFFERENT DOOR SUBMIT A |
| PRODUCT APPROVAL FOR THAT PRODUCT. |
| |
| ANY QUESTIONS CALL ME. |
| |
| ART LANGE |
| BUILDING PLANS EXAMINER |
| 805-6672 |