Plan Review Notes
Plan Review Notes For Permit 05100904
Permit Number 05100904
Review Stop B
Sequence Number 1
Notes
Date Text
2005-12-23 00:00:00DENIED
 1. 713.13(2) F.S.THE NOTICE OF
 COMMENCEMENT MUST BE RE-RECORDED BECAUSE
 THE DESCRIBED IMPROVEMENT OR
 CONSTRUCTION DID NOT COMMENCE WITHIN 90
 DAYS OF RECORDING.
  
 2.SUBMIT TWO ORIGONAL SIGNED AND
 SEALED SURVEYS.
  
 3.ALL PLANS SUBMITTED AFTER OCTOBER 1,
 2005 SHALL BE DESIGNED TO THE 2004 FBC.
  
 4.SUBMIT ENERGY CALCS TO THE 2004 FBC.
  
 5.ENERGY CALCS DO NOT MATCH R- VALUES
 ON PLANS.
  
 6.SUBMIT SPECS FOR HOOD AND GAS BBQ.
 A HOOD IS REQUIRED FOR BUILT IN UNITS.
  
 7.SUBMIT GUARD RAIL DETAILS PER
 R-312.1
  
 8.SUBMIT PRODUCT APPROVAL FOR BITUMEN
 ROOF WITH THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9.PLEASE CLARIFY... IS THE ULTIMATE
 DOOR TO BE USED IN THE FRONT ENTRY?
 IF IT IS A DIFFERENT DOOR SUBMIT A
 PRODUCT APPROVAL FOR THAT PRODUCT.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672