Plan Review Notes For Permit 05100903 |
Permit Number |
05100903 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2006-03-22 00:00:00 | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | PREVIOUS COMMENT: | | | | 1} "IF THE SUBPANEL SHOWN ON THE RISER | | IS FOR A SEPARATE STRUCTURE INDICATE | | COMPLIANCE WITH 250.32 AND 225.32." | | CLEARLY THERE IS A GUEST COTTAGE ON THE | | PROPERTY. THIS BUILDING MUST HAVE A | | DISCONNECTING MEANS AND A GROUNDING | | SYSTEM INSTALLED PER THE ABOVE NOTED | | ARTICLES. PLEASE INDICATE SAME ON THE | | PLAN. SHOW THE LOCATIION OF ALL SERVICE | | EQUIPMENT , INCLUDING THE PANELS AND | | SUBPANELS, ON THE PLAN. DESIGNATE THEM | | FOR CLARITY. | | | | 2} THE GROUNDING ELECTRODE SYSTEM MUST | | ALSO BE BONDED TO BUILDING STEEL SINCE | | IT IS AVAILABLE ON THE PREMISES PER | | 250.52(A)(3). PLEASE INDICATE COMPLIANCE | | ON THE RISER. | | | | | | REGARDING THE ARCHITECT OF RECORD. THE | | TITLE BLOCK MUST COMPLY WITH | | 61G1-16.004, FAC. A COPY OF THE | | CERTIFICATION IS NOTED, BUT THE FAC | | STTES THAT THE AA NUMBER MUST APPEAR IN | | THE TITLE BLOCK. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|