Plan Review Notes
Plan Review Notes For Permit 05100903
Permit Number 05100903
Review Stop E
Sequence Number 3
Notes
Date Text
2006-03-22 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 PREVIOUS COMMENT:
  
 1} "IF THE SUBPANEL SHOWN ON THE RISER
 IS FOR A SEPARATE STRUCTURE INDICATE
 COMPLIANCE WITH 250.32 AND 225.32."
 CLEARLY THERE IS A GUEST COTTAGE ON THE
 PROPERTY. THIS BUILDING MUST HAVE A
 DISCONNECTING MEANS AND A GROUNDING
 SYSTEM INSTALLED PER THE ABOVE NOTED
 ARTICLES. PLEASE INDICATE SAME ON THE
 PLAN. SHOW THE LOCATIION OF ALL SERVICE
 EQUIPMENT , INCLUDING THE PANELS AND
 SUBPANELS, ON THE PLAN. DESIGNATE THEM
 FOR CLARITY.
  
 2} THE GROUNDING ELECTRODE SYSTEM MUST
 ALSO BE BONDED TO BUILDING STEEL SINCE
 IT IS AVAILABLE ON THE PREMISES PER
 250.52(A)(3). PLEASE INDICATE COMPLIANCE
 ON THE RISER.
  
  
 REGARDING THE ARCHITECT OF RECORD. THE
 TITLE BLOCK MUST COMPLY WITH
 61G1-16.004, FAC. A COPY OF THE
 CERTIFICATION IS NOTED, BUT THE FAC
 STTES THAT THE AA NUMBER MUST APPEAR IN
 THE TITLE BLOCK.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW