Plan Review Notes
Plan Review Notes For Permit 05100903
Permit Number 05100903
Review Stop E
Sequence Number 2
Notes
Date Text
2006-02-22 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE THE AIC RATING OF THE SERVICE
 EQUIPMENT PER 110.9.
  
 2} PLEASE INDICATE THE OCP AND CONDUCTOR
 SIZES ON THE PANEL SCHEDULES SO THAT
 BRANCH CIRCUIT COMPLIANCE MAY BE
 REVIEWED.
  
 3} IF THE SUBPANEL SHOWN ON THE RISER IS
 FOR A SEPARATE STRUCTURE INDICATE
 COMPLIANCE WITH 250.32 AND 225.32.
  
 4} A RECEPTACLE IS REQUIRED IN THE
 FAMILY ROOM PER 210.52(A)(2). SEE
 REVIEWED PLAN FOR LOCATION.
  
 5} THERE ARE TWO PANEL #1'S ON THE
 RISER.
  
 REGARDING THE ARCHITECT OF RECORD. THE
 TITLE BLOCK MUST COMPLY WITH
 61G1-16.004, FAC. WHAT IS "DESIGN
 METHODS" ?
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved