Plan Review Notes For Permit 05100903 |
Permit Number |
05100903 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-02-22 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PROVIDE THE AIC RATING OF THE SERVICE | | EQUIPMENT PER 110.9. | | | | 2} PLEASE INDICATE THE OCP AND CONDUCTOR | | SIZES ON THE PANEL SCHEDULES SO THAT | | BRANCH CIRCUIT COMPLIANCE MAY BE | | REVIEWED. | | | | 3} IF THE SUBPANEL SHOWN ON THE RISER IS | | FOR A SEPARATE STRUCTURE INDICATE | | COMPLIANCE WITH 250.32 AND 225.32. | | | | 4} A RECEPTACLE IS REQUIRED IN THE | | FAMILY ROOM PER 210.52(A)(2). SEE | | REVIEWED PLAN FOR LOCATION. | | | | 5} THERE ARE TWO PANEL #1'S ON THE | | RISER. | | | | REGARDING THE ARCHITECT OF RECORD. THE | | TITLE BLOCK MUST COMPLY WITH | | 61G1-16.004, FAC. WHAT IS "DESIGN | | METHODS" ? | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|