Plan Review Notes For Permit 05100903 |
Permit Number |
05100903 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-12-07 00:00:00 | *** DENIED *** | | 1) NEED ENERGY CALCULATIONS ON THE | | ENTIRE HOUSE NOT JUST THE ADDITION ONLY. | | 2) PLEASE CHECK THE SIZE OF THE RETURN | | AIR GRILL ON THE FIRST FLOOR, TWO 18X12 | | GRILLS APPEAR TO BE A 148 SQUARE INCHES | | TO SMALL. | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | TOM GORDON 805-6729 OR PATTY KRAUSS | | 805-6719. |
|